background image

Document ref.: IBVCP  issue 1

Page 20 of 22

For the System Maintainer

 

This section assists the system maintainer to perform preventive maintenance, identify faults, and
expand the system.

Preventive Maintenance

At least once a week, perform a functional test at each Call Point Remote Unit and confirm it can make calls
with the Master and Slave Control Panels.

At least once a month, check the ‘Battery High’, ‘Battery Low’, and ‘Charger’ indicators on the Master and
Slave Control Panels. If any of these indicators are illuminated, replace the batteries. If the indicators are still
illuminated, contact your supplier for advice and service. Note: A fault will sound the beeper, unless silenced.

Call Point Remote Unit Fault Identification

If the yellow indicator by a Call Point Remote Unit button is flashing (except for busy indication, see System
Reset, above) then there is a fault with that unit or the cabling to it. If the fault is cabling it is normal for two
adjacent Call Point Remote Units to indicate a fault, as they are each connected to one end of the same cable.
You can identify the type of fault as follows

1)  Ensure that the Master and Slave Panel’s handsets are on-hook.

2)  Press and hold the 

Speak

 button. If the fault indicator goes out then the Call Point Remote Unit

has a data fault. This is almost certain to be a cable fault.

3)  Press and hold the 

All

 button. If the fault indicator goes out then the Call Point Remote Unit has a

Power fault. This is also likely to be a cable problem.

4)  Press and hold both the 

Speak

 and 

All

 buttons. If the fault indicator goes out then the Call Point

Remote Unit has a fault.

5)  If the fault indicator has not gone out in any of the above it may be a combination of faults. See if

the flashing changes when you press the buttons. If it does, then the described fault is one of
those at the Call Point Remote Unit.

Description of Call Point Remote Unit Controls and Indicators

Volume

: Set as required (normally about half way)

Call Point Remote Unit indicator

: The ‘System OK’ indicator on each of the Call Point Remote Units shows

the status of the unit.

During normal operation two ‘monitoring messages’ are sent around the loop. One originating from connection
‘A’ causes the Call Point Remote Unit to turn their indicators on, ¼ second later the second message is sent
originating from connection ‘B’, this message causes the units to turn their indicators off. This means that on a
system with no cable faults the indicator on each of the Call Point Remote Units will flash once every 1.5
seconds. However if the cable is damaged, units up to the break (starting from connection ‘A’) will have their
indicators on and those after the break will have their indicators off, since they will either only receive on or off
messages.

If a Call Point Remote Unit has not received any data since power was applied it will flash its indicator fast
(about once a second with equal on and off times)

If a Call Point Remote Unit has received data since power was applied but has not received any data for 5
seconds or longer (this should never happen in a working system) then it will flash its indicator slowly (about
once every 14 seconds with equal on and off times)

During commissioning the indicator shows the progression of the initialisation process as described in the
commissioning section.

Expanding the System

The AssureCare system can be expanded to increase the number of Call Point Remote Units, add Slave
Control Panels for larger or more complex systems, and add repeaters where distances between Call Points
are greater than 200m.

Please contact our Technical Sales team on +44(0)1892 664422 for free advice and assistance.

Содержание VIGIL AssureCare

Страница 1: ...can press the Call button on a Call Point Remote Unit to call and speak with a Fire Officer or Building Manager The Fire Officer or Building Manager uses a press to talk telephone handset at their ded...

Страница 2: ...o conform to the following EC standards EMC EN 55103 1 Environment E1 EN 55103 2 E5 Safety EN 60065 Failure to install or use the equipment in the manner described in the product literature will inval...

Страница 3: ...e cabling a further 200m For systems with larger numbers of Call Point Remote Units multiple circuits ring sections are used The terminations of each circuit are made at the Main Control Panel to form...

Страница 4: ...ring circuit The terminal blocks labelled TB1 are located in the top of the Control Panel enclosure and the terminations for Call Point Remote Units 1 and 16 are also shown in detail CAN H CAN L V 0V...

Страница 5: ...ocument ref IBVCP issue 1 Page 5 of 22 Cabling Design and Installation Recommendations cont Configuration Example 2 TB1 FIRST BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP LAST BVCP...

Страница 6: ...bling Design and Installation Recommendations cont Configuration Example 3 Typical Connection Diagram Up To 48 Units TB1 FIRST BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP LAST BVCP BVC...

Страница 7: ...d Installation Recommendations cont Configuration Example 4 Typical Connection Diagram Up To 64 Units TB1 FIRST BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP BVCP LAST BVCP BVCP BVCP BVCP BVC...

Страница 8: ...E BOARD 64 way SLAVE 2 INTERFACE BOARD 16 way MASTER CONTROL PANEL 96 way 800m MAX 25 TELEPHONES These distances have been calculated for 1 5sqmm conductors Please contact our Technical Sales team on...

Страница 9: ...system are related to the Control Panel buttons as follows Call Point Remote Unit Button Call Point Remote Unit Button 1 1 9 9 2 2 10 10 3 3 11 11 4 4 12 12 5 5 13 13 6 6 14 14 7 7 15 15 8 8 16 16 For...

Страница 10: ...Installing Control Panels 47 0 0 0 363 0 13 5 396 5 0 0 52 5 385 0 1 Open the glazed door and remove the M6 screw s from the right hand side of the Control Panel 2 To allow access to the two top locat...

Страница 11: ...es For Mounting 128 Zone Control Unit 4 wire Ring IN 4 wire Ring OUT View of cable terminations to Control Unit Termination Panel Note In this example the ring consists of one circuit of Call Point Re...

Страница 12: ...o 1 4m from the floor but at 900mm to 1 2m in refuges 2 At the rear of the Remote Unit remove the screw to release the bracket retaining the blue termination block 3 Terminate all cables at the termin...

Страница 13: ...re the system and confirm it is functioning correctly Commissioning must be carried out on a new system or if a Remote has been added or replaced To commission this product you will need A small flat...

Страница 14: ...ll Point Remote Units See following table Terminals B Terminals C CAN H Connect to CAN H CAN L Connect to CAN L 4 Connect mains power to the Control Panel but do not connect the batteries 5 At the Con...

Страница 15: ...until the yellow indicator by button 1 starts to flash then release it Press and release the Fault Accept button to silence the fault buzzer 14 During commissioning a special code is sent round the ri...

Страница 16: ...Remote Unit in turn check that its indicator is pulsing before making a call to the control panel to confirm correct operation and the Call Point Remote Unit s number Master Control Panel System 65 to...

Страница 17: ...twice as fast as the others The offset is 0 to15 and the range 1 to 16 To change the settings the first button push sets the offset the next sets the range and the next toggles between master and nor...

Страница 18: ...Document ref IBVCP issue 1 Page 18 of 22...

Страница 19: ...sert Labels cont Slide the strips cut from the Zone Insert template under the membrane at the positions shown in the picture They can be inserted from either side Note Zone Insert Template is also ava...

Страница 20: ...flashing changes when you press the buttons If it does then the described fault is one of those at the Call Point Remote Unit Description of Call Point Remote Unit Controls and Indicators Volume Set a...

Страница 21: ...inate when the Battery voltage is low Charger fault LED Will illuminate if the batteries are unable to hold their charge or if they are not fully charged after 24 Hours charging Reset must be pressed...

Страница 22: ...ll Communications Ltd reserves the right to make changes to product specification without notice or liability Information contained in this document is believed to be accurate however no representatio...

Страница 23: ...emergency call point system which has been developed in accordance with BS5839 part 9 and BS5588 The system is a fully monitored and battery backed communication network and has capabilities to funct...

Страница 24: ...ng mode then press and hold the button on handset base or SPEAK on the control panel Avoid distortion of your speech by keeping the SPEECH LEVEL LEDs below the maximum red indication You will be unabl...

Страница 25: ...he Remote Unit will ring and so will the handset s at the Control Panel s When the person at the control panel answers wait for them to finish speaking before trying to speak back they cannot hear you...

Страница 26: ...y is given and Baldwin Boxall Communications Ltd assumes no liability with respect to the accuracy of such information Use of Baldwin Boxall Communications Ltd products as critical components in life...

Страница 27: ...de as follows To ensure correct operation both JP1 and JP2 must be fitted If the fire panel connections or the Test connections to the Break Glass Unit are not in place the System will Commission corr...

Отзывы: