OmniCare EVC System
Installation & Commissioning Manual
OmniCare issue 1
83
C
O
M
M
U
N
I
C
A
T
I O N S
6.4.2 Battery Condition Monitoring
The Battery Charger in the OmniCare EVC System system not
only charges the batteries, but also monitors the condition of
them to detect battery degradation.
• If the charger runs continuously for more than 24 hours (i.e.
batteries have not reached 27.6 V DC within 24 hours), then
the “Charger Fault” LED will be illuminated.
• If the battery voltage falls to 24.0V DC within 6 minutes of
the charger finishing (i.e. battery voltage drops from 27.6V
DC to 24.0V DC) then the “Charger Fault” LED will be
illuminated.
• The Battery High LED illuminates at 28VDC.
• The Battery Low LED illuminates at 20VDC.
• If the Battery HIGH and Battery LOW LEDs are both
illuminated then the Batteries are disconnected.
Battery disconnect occurs at 20VDC, (if running on batteries).
N
OTE
: Serviceable batteries should reach 27.6V DC within 24 hours.
N
OTE
: Serviceable batteries should hold charge for longer than 6
minutes.
N
OTE
: If Batteries are reconnected while Mains is still connected and
their voltage is less than 20V DC the charger will not restart.
Содержание OmniCare
Страница 54: ...OmniCare EVC System Installation Commissioning Manual 46 OmniCare issue 1 C O M M U N I C A T I O N S...
Страница 72: ...OmniCare EVC System Installation Commissioning Manual 64 OmniCare issue 1 C O M M U N I C A T I O N S...
Страница 76: ...OmniCare EVC System Installation Commissioning Manual 68 OmniCare issue 1 C O M M U N I C A T I O N S...
Страница 92: ...OmniCare EVC System Installation Commissioning Manual 84 OmniCare issue 1 C O M M U N I C A T I O N S...
Страница 99: ...OmniCare EVC System Installation Commissioning Manual OmniCare issue 1 91 C O M M U N I C A T I O N S...
Страница 101: ...OmniCare EVC System Installation Commissioning Manual OmniCare issue 1 93 C O M M U N I C A T I O N S...