Figure 4.3 — Advance Remote Unit System OK LED
The first unit that failed to return a Red indication should
display one of the above conditions which will indicate which
cable(s) are at fault.
10. When the total number of illuminated LEDs is the same as
the number of Remote Units on the ring, disconnect the
Mains Power and connect the other end of the ring to the “B”
connection (or to the “D” connection if “B” and “C” have been
linked) on the Control Panel.
11. Reconnect the Mains Power and initiate the commissioning
process again (press SPEAK and RESET buttons).
N
OTE
: For further information on diagnosing faults refer to “Fault
Finding” on page 69.
C
A U T I O N
Ensure Mains Power and batteries are disconnected before
connecting or disconnecting Ring Circuits.