Customizing Your Application 8-1
MN767S
Chapter 8
Customizing Your Application
8.1 Simple Parameter Adjustments
Factory settings may give satisfactory performance, however certain adjustments may be beneficial.
Table 8-1
Adjustment
Parameter
Parameter Name
Motor Rated Volts
P1-01
The factory default setting P1-01 = 575 should be used unless voltage
compensation is required.
Motor Rated Current
P1-02
Must be set to the value on the motor nameplate.
P1-04 is optional. If this parameter is set to zero (default state), speed is
displayed in Hz (otherwise, RPM).
Motor Rated Frequency
P1-03
Motor Rated Speed
P1-04
Minimum Speed
P1-05
Set P1-06 to the maximum speed and P1-05 to the minimum speed. These limits
can also be negative for reverse speeds. If a non-zero minimum speed is set in
P1-05, the motor will ramp to this minimum speed at the
rate set in P1-10 as soon as the drive is enabled.
Note:
If P1-04 is set to a value other than “0”, the value displayed will be in RPM.
Maximum Speed
P1-06
Start/Stop Source
P1-07
Set as required by the application.
Speed Ref Source
P1-08
Set as required by the application.
Stop Mode
P1-09
Select method of stopping required when drive is disabled.
Acceleration Ramp
P1-10
Adjust as need for your application. Short Acceleration or Deceleration times may
cause excess motor current and may result in it tripping or the motor stalling.
Deceleration Ramp
P1-11
Analog Input Format
P2-30
Set as required by the application (0-10V, 10-0V, 4-20mA)
Содержание VS1STS Series
Страница 1: ...10 11 Installation Operating Manual MN767S VS1STS AC Microdrive ...
Страница 6: ...iv MN767S ...
Страница 28: ...5 8 Control Wiring MN767S ...
Страница 50: ...8 2 Customizing Your Application MN767S ...
Страница 54: ...9 4 Troubleshooting MN767S ...
Страница 56: ...A 2 Technical Specifications MN767S ...
Страница 68: ...D 2 Options and Kits MN767S ...
Страница 72: ...E 4 RS485 MODBUS Protocol MN767S ...