Receiving & Installation  3‐3

MN2418

Electrical Connections

   All load connections are made at the panel using electrical cords with the proper

mating plug for the receptacle being used.  More than one receptacle can be used as long as the
total load does not exceed the continuous rating of the generator.

WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician

has installed an approved transfer switch.  The National Electrical Code (NEC) requires that
connection of a generator to any electrical circuit normally powered by means of an electric
utility must be connected by means of approved transfer switch equipment so as to isolate
the electrical circuit from the utility distribution system when the generator is operating.
Failure to isolate the electrical circuits by such means may result in injury or death to utility
power workers due to backfeed of electrical energy onto the utility lines.

Use correct size insulated wire to connect the generator to the load. The gauge of the wire will
depend on the distance to the load, the permissible voltage drop at the load, and the current
required by the load. If you are not sure of the gauge wire needed for your application, consult a
competent electrician.  Using wire that is too small can result in fire hazard.  Also, be sure the
wire has the appropriate ratings for insulation and environment conditions.
The correct mating connector must be used to fit the connectors provided on the operator panel
of your generator. Table 3‐1 describes the connector types provided (receptacles) and the load
characteristics to help you choose the correct size wire.  Figure 3‐2 shows the receptacles.

Table 3‐1  Single Phase Power Receptacle Description

Model

Electrical Connection Information (Receptacle Provided at Panel)

Straight 120VAC

(20Amp)

Twist Lock 120/240VAC

(30Amp)

Rated Watts/ 

(Full load Amps 120/240)

PG6000

2- 520R  120VAC

1- L1430R 120/240VAC

5700 / (44.2/22.1)

Class 1 wiring methods must be used for field wiring connections to terminals of a Class 2 circuit.

Figure 3‐2  Receptacle Connections 

 

(GOLD)

X

G

W

(SILVER)

Y

(GOLD)

NEMA

L14-30R

125/250V

30A

NEMA 520R

125V 20A

Ground

Neutral

120VAC

120VAC

Содержание PG 6000

Страница 1: ...PG 6000 Generator Installation Operating Manual 8 06 MN2418...

Страница 2: ...hemicals known to the state of California to cause cancer birth defects and other reproductive harm WARNING CALIFORNIA PROPOSITION 65 WARNING Battery posts terminals and related accessories are known...

Страница 3: ...3 1 Storage 3 1 Physical Location 3 2 Installation 3 2 Electrical Connections 3 2 Frame Ground Connection 3 3 Engine Oil 3 4 Recommended Engine Oil 3 4 Use of Electric Motor Loads 3 4 Optional Wheel K...

Страница 4: ...ii Table of Contents MN2418...

Страница 5: ...uipment at all times Keep non qualified personnel at a safe distance from this equipment Only qualified personnel familiar with the safe installation operation and maintenance of this device should at...

Страница 6: ...should not be attempted Never start the engine unless you have first verified that the installation and operation of the generator are as described in this manual WARNING Be sure that you are complete...

Страница 7: ...t whenever engine is running Electrical shock can cause serious or fatal injury Never operate electrical equipment while standing in water on wet ground or with wet hands feet or shoes or while barefo...

Страница 8: ...extremities and cause serious or fatal injury WARNING Unauthorized modification of a generator set may make the unit unsafe for operation or may impair the operation of the unit Never start a generato...

Страница 9: ...nk indoors or in an enclosed poorly ventilated area where gasoline fumes could reach an ignition source and cause an explosion Caution Statements Caution The brass connecting tab on some 120VAC duplex...

Страница 10: ...1 6 Product Safety Information MN2418...

Страница 11: ...nstallation shipment or otherwise Problems with Baldor products can be due to improper maintenance faulty installation non Baldor additions or modifications or other problems not due to defects in Bal...

Страница 12: ...2 2 General Information MN2418...

Страница 13: ...ad the following guidelines prior to storing the unit 1 Remove all fuel from the engine s fuel tank 2 Start the generator set and allow it to run out of fuel 3 Close all the fuel valves Note An altern...

Страница 14: ...se severe illness or death Never breath exhaust fumes produced by a running engine Only run the engine outdoors where ventilation is plentiful Exhaust gases contain carbon monoxide a colorless odorles...

Страница 15: ...he generator to the load The gauge of the wire will depend on the distance to the load the permissible voltage drop at the load and the current required by the load If you are not sure of the gauge wi...

Страница 16: ...ch more current amperes to start them than to keep them running Some motors particularly split phase motors are very difficult to start and require 5 to 7 times more current to start them Repulsion in...

Страница 17: ...censed electrician has installed an approved transfer switch Multiple receptacles may be used at the same time provided the total electrical load does not exceed the generators rated output 120Volts P...

Страница 18: ...rope to snap back into the recoil housing Note If the engine does not start after several attempts smell for fuel near the air cleaner If there is a significant gasoline smell coming from the air clea...

Страница 19: ...er s manual 4 Replace the spark plug s as is recommended by the engine manufacturer 5 Clean the cooling fins on the engine to keep the engine s heat dissipation potential at it s maximum 6 Inspect and...

Страница 20: ...orque of terminals Replace worn bearing Low output voltage Low engine speed Excessive load High resistance connections connections will be warm or hot Shorted field Low power factor Check that the Aut...

Страница 21: ...replacing a receptacle inspect the brass tab that normally links both receptacles If it is removed be sure to remove the brass tab from the replacement receptacle before it is installed Failure to re...

Страница 22: ...A 2 PowerchiefR Series MN2418 Figure A 2 PG6000 Wiring Diagram...

Страница 23: ...arranty on EVAP emission related parts is as follows Any warranted part that is not scheduled for replacement as required maintenance in the written instructions supplied is warranted for the warranty...

Страница 24: ...this product contains chemicals known to the state of California to cause cancer birth defects and other reproductive harm WARNING CALIFORNIA PROPOSITION 65 WARNING Battery posts terminals and related...

Страница 25: ...Baldor District Offices...

Страница 26: ...he state of California to cause cancer birth defects and other reproductive harm WARNING CALIFORNIA PROPOSITION 65 WARNING Battery posts terminals and related accessories are known to the state of Cal...

Отзывы: