7. Special conditions of use 

7.1. 

Y237 

can ONLY be mounted on instruments manufactured by Dresser Produits Industriels S.A.S. 

7.2.  For ambient temperature greater than 70°C, the user must choice a cable entry and a cable 

compatible with: 

Ambient Temperature 

Cable Temperature 

75°C 

80°C 

80°C 

85°C 

85°C 

90°C 

 

7.3.  Y237 is intended to be used in an ambient temperature from -55°C to +85°C. 

7.4.  The cable entry and the cable must be compatible with the minimum temperature of -55°C. 

7.5.  If a cable input from the 

Y237

 adaptor is not used, the hole must be closed by a plug, depending on 

the size of the tapping involved. 

7.6.  In case of two cable gland entries not used, the 

Y237

 must be removed. 

7.7.  The plug must be directly screwed on the 

Y237

7.8.  Adaptor or reducer are not allowed. 

7.9.  The external thread (male) shall be cemented with high-strength threadlocker type Loctite 2700 or 

equivalent product with similar efficiency to secure the 

Y237

 in the intended direction. 

7.10. The supply of cable gland, plug and the mounting on the conduit connection can be made by the end 

user with respect to the mounting rules defined in the 

Annex

7.11. For use in dusty hazardous areas (zone 21 & 22), the user will have to proceed to a cleaning 

regularly the different sides of the enclosure to avoid the deposits of dusts, the maximum thickness 
must be <5 mm. This cleaning will be done with respect to the next requirement 

§7.12.

 

It  is  recommended  for  safe  operation,  the  local  conditions  around  the  device  are  free  of 
potentially explosive atmosphere. 

7.12. To avoid the risk of ignition from electrostatic discharge it shall be necessary to follow the guidance 

of 

IEC/TS 60079-32-1

 for example to clean the device with a wet rag. 

It  is  recommended  for  safe  operation,  the  local  conditions  around  the  device  are  free  of 
potentially explosive atmosphere. 

7.13. The user will have to check the temperature increase on the 

Y237

 adaptor coming from the 

mechanical part in contact with it or through the process thermal radiation be less or equal than the 
temperature classification allowed. This must be done in conformance with 

EN/IEC 60079-14

 and / 

or national and local regulations applicable for explosible atmospheres. 

7.14. The flameproof joints are not intended to be repaired. 

7.15. Potential danger of electrostatic charges: see instructions. 

7.16. The other conditions of use are stipulated in the instructions. 

Содержание Masoneilan Y237

Страница 1: ...Baker Hughes Data Classification Public Masoneilan Y237Model Adaptor for Multiple Cable Entries ATEX Instruction Manual Rev B...

Страница 2: ...REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE MET IN...

Страница 3: ...Adaptor ATEX Instruction Manual 3 Table of Contents 1 Y237 Operation 5 2 General requirements 5 3 Numbering System 5 4 Marking 6 5 Installation and electrical connections 7 6 Maintenance and service 7...

Страница 4: ...Installed put into service and maintained by qualified and competent professionals who have undergone suitable training for instrumentation used in areas with potentially explosive atmosphere Such tr...

Страница 5: ...f the Y237 on an electrical instrument according to ATEX 2014 34 EU directive The essential health and safety requirements stated into annex II of the 2014 34 EU Directive has been satisfied 2 General...

Страница 6: ...Dresser Produits Industriels S A S 14110 CONDE SUR NOIREAU FRANCE Type designation Y237 See numbering system 3 for complete codification Basic marking II 2 G D Complementary marking Ex db IIC Gb et E...

Страница 7: ...minum S Stainless Steel 3 NPT 4 NPT 4 NPT 5 NPT 6 M20 1 The three female inputs are identical on the Y237 If one Y237 input is not used the conduit will be closed by a plug if apparatus certified ATEX...

Страница 8: ...end user with respect to the mounting rules defined in the Annex 7 11 For use in dusty hazardous areas zone 21 22 the user will have to proceed to a cleaning regularly the different sides of the enclo...

Страница 9: ...iciency Cemented with Loctite 5400 low strength thread sealant or equivalent product with similar efficiency This is mandatory to meet an IP67 Tightening torque see Cable Gland instruction manual Chec...

Страница 10: ...erhughes com Copyright 2021 Baker Hughes Company All rights reserved Baker Hughes provides this information on an as is basis for general information purposes Baker Hughes does not make any representa...

Отзывы: