Modem and Computer Use in Intrinsically Safe Circuits
Many HART
®
modems that are in use today are not approved for connections to Intrinsically
Safe control circuits. Most portable computers are NOT approved for use in hazardous areas.
Modems can be safely connected to the safe area side of barriers, and isolators. Observe
requirements for the HART
®
filter.
MACTek
®
Intrinsically Safe modem
The VIATOR RS232 HART
®
Interface [Eex ia] IIC complies with the Essential Health and Safety
Requirements relating to the design and construction of equipment and protective systems
intended for use in potentially explosive atmospheres. Requirements given in Annex II of the
Directive 94/9/EC (ATEX Directive) of the European Parliament and the Council of 23 March
1994. Consult MACTek
®
Corporation, http://www.mactekcorp.com/company.html for detailed
requirements for safe use.
MACTek
®
Warning
"This product has not been tested by any certification agency such as Factory Mutual with
jurisdiction outside the European Union for intrinsic safety. The product can be used outside
the European Union (e.g. in the USA) on the sole authority of the buyer. MACTek
®
makes no
claims of suitability and offers no warranties regarding the use of this product for connection
of PCs to circuits extending into hazardous areas in countries outside the European Union."
Do not connect a PC or HART
®
modem to an intrinsically safe circuit except on the safe area
side of a barrier. Do not operate a PC in a hazardous area without compliance with local and
plant regulations.
Use of Handheld Communicators In Intrinsically Safe Circuits
WARNING
Ensure that any handheld communicator in use is approved for
use in hazardous areas that use explosion proof safety practices.
Do not use unapproved handheld communicators unless the area
has been declared safe (Hot Work Permit).
If a HART
®
communicator is approved to communicate with
intrinsically safe control circuits in hazardous areas. Read the
product manual before use and observe all warnings. The intrinsic
safety entity parameters must be added to the SVI II AP entity
parameters to determine suitability for use in any intrinsically safe
circuit. Observe the labels on the handheld communicator or
consult the manufacturer.
Содержание Masoneilan SVIII AP
Страница 10: ...This page intentionally left blank...
Страница 14: ...This page intentionally left blank...
Страница 18: ...This page intentionally left blank...
Страница 58: ...This page intentionally left blank...
Страница 68: ...This page intentionally left blank...
Страница 104: ...This page intentionally left blank...
Страница 122: ...This page intentionally left blank...
Страница 128: ...This page intentionally left blank...
Страница 148: ...This page intentionally left blank...
Страница 158: ...2017 Baker Hughes a GE company LLC All rights reserved 158 BHGE Spare Parts...
Страница 159: ...Masoneilan SVI II AP Installation and Maintenance Manual 159 2017 Baker Hughes a GE company LLC All rights reserved...
Страница 160: ...2017 Baker Hughes a GE company LLC All rights reserved 160 BHGE...
Страница 162: ...This page intentionally left blank...
Страница 166: ...This page intentionally left blank...
Страница 172: ...This page intentionally left blank...
Страница 174: ...This page intentionally left blank...
Страница 176: ...This page intentionally left blank...
Страница 180: ...This page intentionally left blank...
Страница 188: ...This page intentionally left blank...
Страница 190: ...This page intentionally left blank...
Страница 203: ......