6.  Assembly of a 7700E Positioner on a Valve 

 

 

Comply with current national and local regulations for electrical installation work. 

 

Must be installed and put into service in conformance with EN/IEC 60079-14 and / or national and 
local regulations applicable for explosive atmospheres. 

 

Comply with national and local explosive atmosphere regulations. 

 

Before carrying out any work on the device, power off the instrument or make sure that the local 
conditions in the potentially explosive atmosphere permit the safe opening of the cover. 

 

Before switching on or after doing any work on the device, always tighten the cover (C) with a 
seal (J) in good condition and put back the safety screw (V). 

 

Note: Before installation, check that the device is undamaged. In the event of damage, replace the 
defective parts with genuine manufacturer's replacement parts. 
 

If the positioner is shipped alone, the user is responsible for its installation, electrical and pneumatic connections 
and its calibration. 

 

Please refer to 28000 Series instruction manual Ref. 

30857 

for more details. 

 
 

7.  Pneumatic Connection of Positioner 7700E 

 

Make sure that the air supply pressure is suitable for the installation and for the instrument. 
When using a positioner, make sure that the air supply pressure matches the one specified on the 
serial plate without exceeding 275 kPa (40 psi). 

 

Diameter of tubing required: 4 x 6 mm. 

 

 

8.  Electrical Connection, Installation and Start-Up 

 

 

Comply with current national and local regulations for electrical installation work. 

 

Must be installed and put into service in conformance with national and local regulations 
applicable for explosible atmospheres. 

 

Before carrying out any work on the device, power off the instrument or make sure that the local 
conditions in the potentially explosive atmosphere permit the safe opening of the cover. 

 

Connect  the  wires  to  the  instrument

’s  terminals  taking  care  of  complying  with  polarities  and 

maximum voltage allowed. 

 

Before  switching  on  or  after  doing  any  work  on  the  device,  always  tighten  the  cover  (C)  with  a 
seal (J) in good condition and put back the safety screw (V). 

 

Check the earth terminals are well connected. 

 

Note

Before  installation,  check  that  the  device  is  undamaged.  In  the  event  of  damage,  replace  the 
defective parts with genuine manufacturer's replacement parts.

 

Содержание Masoneilan 7700E

Страница 1: ...Baker Hughes Data Classification Public Masoneilan Type 7700EElectro Pneumatic Positioner with I P 4000 Converter Ukrainian UA TR Instruction Manual Rev A...

Страница 2: ...REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE MET IN...

Страница 3: ...Assembly of a 7700E Positioner on a Valve 7 7 Pneumatic Connection of Positioner 7700E 7 8 Electrical Connection Installation and Start Up 7 8 1 Conduit entry in flameproof application 8 8 2 Electrica...

Страница 4: ...y qualified and competent professionals who have undergone suitable training for instrumentation used in areas with potentially explosive atmospheres Such trainings are not supported by Baker Hughes I...

Страница 5: ...pneumatic signal Model 7700E electro pneumatic positioner can be used only on Varipak valve 28000 2 Numbering System Unique positioner 7700 E with I P 4000 module Different versions Housing material...

Страница 6: ...Pi 0 33 W Li 0 Ci 0 IP66 Warning Potential electrostatic charging hazard See instructions for safe use 5 Flameproof Marking and Electrical Safety Parameters The marking on the serial plate stamped on...

Страница 7: ...Series instruction manual Ref 30857 for more details 7 Pneumatic Connection of Positioner 7700E Make sure that the air supply pressure is suitable for the installation and for the instrument When usin...

Страница 8: ...y on the single NPT ANSI ASME B1 20 1 housing conduit connection The cable entry has to be suitable to the equipment operating zone IP 6X for zones 20 21 and 22 If an adaptor or reducer is needed it m...

Страница 9: ...allation for explosible atmosphere with d protection mode Intrinsically safe installation for explosible atmosphere with ia protection mode Note It is under the user responsibility to check the instal...

Страница 10: ...ke sure that the local conditions in the potentially explosive atmosphere permit the safe opening of the cover Connect the wires to the instrument s terminals taking care of complying with polarities...

Страница 11: ...ment are not damaged In the event of damage replace the defective parts with genuine manufacturer s replacement parts Pay particular attention to the following o General condition of the housing o Che...

Страница 12: ...vertical position uppermost the required ingress protection against water is invalidated therefore it shall only be installed in this orientation if its location provides protection against falling wa...

Страница 13: ...ss 123112 Russia Moscow Presnenskaya embankment house 10 room III floor 3 room 22 Tel 7 495 739 68 11 MoscowHelpDesk bakerhughes com 14 Design and Manufactured by Products are designed and controlled...

Страница 14: ...PT requirements of ANSI ASME B1 20 1 A minimum of 5 threads provided on each part MOUNTING RULE Thread cleaning with Loctite 7063 or equivalent product with similar efficiency Cemented with Loctite 27...

Страница 15: ...com Copyright 2021 Baker Hughes Company All rights reserved Baker Hughes provides this information on an as is basis for general information purposes Baker Hughes does not make any representation as t...

Отзывы: