background image

Masoneilan Model 4411 Electropneumatic Transducer Instruction Manual  |  8 

Copyright 2020 Baker Hughes Company. All rights reserved.

Instructions Specific to  

Hazardous Area Installations

(Reference European ATEX Directive 2014/34/EU, Annex II, 

1.0.6)

The  following  instructions  apply  to  equipment  covered  by 

certificate numbers SIRA 01ATEX2224X & SIRA 01ATEX1223
1.   The  Model  4411  may  be  installed  as  intrinsically  safe  or 

flameproof:

 

• 

 Zone 0 or 20 installations require the equipment to be 

installed  as  intrinsically  safe  via  suitable  associated 

apparatus�

 

• 

 Zone 1 or 21 installations require the equipment to be 

installed as intrinsically safe or flameproof; if installed 

as  flameproof,  associated  apparatus  is  not  required, 

but  there  are  more  onerous  requirements  for  cable 

entry – refer to EN60079-0.

 

• 

 Zone 2 or 22 installations may be intrinsically safe or 

flameproof.

 

•   It is recommended that the installer indicates on the 

equipment which certification code applies.

2.   The  equipment  should  not  be  used  outside  the  stated 

ambient temperature range.

3.   The equipment has not been assessed as a safety-related 

device  (as  referred  to  by  Directive  2014/34/EU  Annex  II, 

clause 1.5).

4.   Installation  and  maintenance  of  this  equipment  shall  be 

carried  out  by  suitably-trained  personnel  in  accordance 

with the applicable codes of practice (EN 60079-14 and EN 

60079-17 within Europe).

5.   Repair  of  this  equipment  shall  be  carried  out  by  the 

manufacturer or in accordance with the applicable code of 

practice (IEC 60079-19).

6.   When  installing  the  equipment  as  flameproof  cable  gland 

(M20 parallel thread) or a conduit (1/2" NPT tapered thread), 

the installer should verify the thread form and ensure that 

the appropriate matching thread is used� The pneumatic 

connections are not flameproof entries.

7.   The  certification  of  this  equipment  relies  on  the  following 

materials used in its construction:

 

Enclosure:  aluminium alloy and zinc alloy

 

O-ring:  nitrile rubber

 

Encapsulant: polyurethane

If the equipment is likely to come into contact with aggressive 

substances, then it is the responsibility of the user to take suitable 

precautions that prevent it from being adversely affected, thus 

ensuring that the type of protection is not compromised.
• 

 Aggressive  substances:  e.g.  acidic  liquids  or  gases  that 

may  attack  metals,  or  solvents  that  may  affect  polymeric 

materials�

• 

 Suitable precautions: e.g. regular checks as part of routine 

inspections  or  establishing  from  the  material’s  data  sheet 

that it is resistant to specific chemicals.

• 

 Not to be used with pure oxygen or oxygen enriched media 

as the process fluid.

Consult the supplier for approval certificates.
8.   Only  approved  cable  glands  are  to  be  used  which  must 

maintain an Ingress Protection of IP66.

9.   Unused entry port hole must be blanked off using suitably 

approved blanking plug conforming to the hazardous area 

certification rating applicable.

Instructions – Special 

Condition for Safe Use 

For Certificate Number Sira 01ATEX1223 – (Ex d) None.
For Certificate Number Sira 01ATEX2224X – (Ex ia)
1.   For operation reasons, it may be necessary to connect the 

screen  of  the  cable  to  the  enclosure  of  the  equipment  in 

the hazardous area. If this is the case, then the equipment 

shall  be  installed  in  accordance  with  EN  60078-14:2014 

(specifically  clause  16.2.2.3  and  16.2.4),  typically  using  a 

galvanically-isolated  interface  with  no  other  connection  to 

Earth apart from via the enclosure of the equipment.

2.   The enclosure is made from light metal which could cause 

ignition due to impact and friction. This shall be taken into 

consideration when the apparatus is installed in location that 

specifically requires equipment protection level Ga.

3.   Under  certain  extreme  circumstances,  the  non-metallic 

parts incorporated in the enclosure of this equipment may 

generate  an  ignition-capable  level  of  electrostatic  charge. 

Therefore,  when  it  is  used  for  applications  that  specially 

require equipment protection level Ga, the equipment shall 

not be installed in a location where the external conditions 

are  conductive  to  the  build-up  of  electrostatic  charge  on 

such  surfaces.  Additionally,  the  equipment  shall  only  be 

cleaned with a damp cloth.

4.   The option for the air vented from the enclosure to be re-

circulated and introduced back into the process stream shall 

not be used when the equipment is installed in locations that 

specifically require equipment protection level Ga for group 

II category 1G or 1D for group III category 1D equipment.

Содержание Masoneilan 4411 I.S.

Страница 1: ...Masoneilan 4411 Series Electropneumatic Transducer Instruction Manual Baker Hughes Data Classification Public...

Страница 2: ...CULAR REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE ME...

Страница 3: ...tured Bleed Version 3 Pneumatic Installation 3 Electrical Installation 4 Wiring and Cable Entry 4 Conduit Entry 4 Calibration 4 Tight Shut Off Adjustment Instructions 5 Simple Functional Checks 5 Tech...

Страница 4: ...ne Warranty Items sold by Baker Hughes are warranted to be free from defects in materials and workmanship for a period of one year from the date of shipment provided said items are used according to B...

Страница 5: ...rocess control applications The units operate a closed loop system incorporating a feedback sensor ensuring long term stability and high accuracy performance with fail safe operation i e the output fa...

Страница 6: ...be blocked with paint and or plastic sheeting etc Captured Bleed Version The baffles and the baffle cover are fitted to maintain the adequate Ingress Protection IP rating of the instrument Removal of...

Страница 7: ...conforming to explosion proof specifications must be used A ground terminal is provided both internally and externally and should be used if ground continuity is essential The unit is supplied with pl...

Страница 8: ...p pressure 0psi adjust potentiometer slowly clockwise until the output pressure falls to zero Do not turn the pot beyond this point The shut off point is now set Shut off point check Increase the inpu...

Страница 9: ...accordance with ANSI ISA 51 1 1993 N B Instrument accuracy excludes calibration errors Temperature Effect Span and Zero Mean temperature coefficient over full operating range 40 to 85 C less than 0 0...

Страница 10: ...III Division 2 Group FG T6 Ta 75 C T5 Ta 85 C CSA Class I Division 1 Group BCD Class II Group EFG Class III Ta 85 C T5 Ta 65 C T6 Class I Division 1 Group ABCD Class II Group EFG Class III Ta 85 C T4...

Страница 11: ...being adversely affected thus ensuring that the type of protection is not compromised Aggressive substances e g acidic liquids or gases that may attack metals or solvents that may affect polymeric ma...

Страница 12: ...9 Baker Hughes Copyright 2020 Baker Hughes Company All rights reserved...

Страница 13: ...Masoneilan Model 4411 Electropneumatic Transducer Instruction Manual 10 Copyright 2020 Baker Hughes Company All rights reserved...

Страница 14: ...11 Baker Hughes Copyright 2020 Baker Hughes Company All rights reserved Notes...

Страница 15: ...Masoneilan Model 4411 Electropneumatic Transducer Instruction Manual 12 Copyright 2020 Baker Hughes Company All rights reserved Notes...

Страница 16: ...ormation The Baker Hughes logo and Masoneilan are trademarks of Baker Hughes Company Other company names and product names used in this document are the registered trademarks or trademarks of their re...

Отзывы: