To  meet  the  EMC  specifications,  screened  cable  should  be 

used for installation. The cable screen should be connected to 

the internal earth bonding point of the I/P. An earth strap should 

also  be  connected  from  the  external  earth  bonding  point  of 

the I/P to a common earth point. The cable screen should not 

be  connected  at  the  signal  source  when  used  in  Intrinsically 

Safe (IS) environments. The I/P has been thoroughly tested in 

accordance with:

Electromagnetic compatibility (EMC) 

Generic Standards – Immunity for industrial environments 

Electromagnetic compatibility (EMC) 

Generic Emissions Standard – Industrial environment
Please consult wiring diagram for further information. The results 

obtained from these tests show that with the screen arrangement 

shown in the installation diagram, the typical sustained output 

pressure  shift  is  <+/-5%  full  scale.  Consult  supplier  for  further 

details�

Instrument Mounting

The converter can be mounted directly onto a valve, onto any 

suitable flat surface, or onto 2” (50mm) pipe. Dimensional details:

Figure 2 

These  converters  will  operate  in  any  position,  with  slight  re-

calibration  adjustments,  normal  operation  is  in  the  upright 

position, i.e. with the screwed lid horizontal. The unit is weather 

resistant when the lid is removed for connection or calibration, 

but should not be left uncovered during operation or for extended 

periods of time. They are unaffected by shock and vibration, but 

severe vibration environments are best avoided.
The instruments are protected against environmental effects, to 

a level of Type 4X (IP66). Sensible positioning should be used if 

the local environment is severe.
Temperature  compensation  is  designed  into  these  converters 

which  will  operate  over  a  range  from  –40°  to  +85°C  (-40°  to 

+185°F). Maximum life is obtained if extreme temperature cycling 

is avoided. In extreme direct sunlight, sun-shading is advised.
The  pneumatic  exhaust  and  the  bleed  are  routed  through  the 

baffles. The baffles must not be blocked with paint and/or plastic 

sheeting etc�

Captured Bleed Version

The baffles and the baffle cover are fitted to maintain the adequate 

Ingress Protection (IP) rating of the instrument. Removal of these 

protective parts will invalidate the IP and the NEMA 4X rating of 

the instrument�

For  captured  bleed  installation,  remove  the  baffle  cover  and 

unscrew  both  the  baffles,  fit  1/8"  NPT  fittings  to  two  separate 

lengths  of  pipes,  to  exhaust  and  bleed  gas  to  a  safe  area 

installation� 

Vented  gas  from  the  enclosure  through  bleed  port  must  not 

be  re-circulated  and  introduced  back  into  the  process  stream. 

Exhaust port installation must not have any restriction to create 

backpressure  to  cause  instrument  to  malfunction.  Instrument 

installation  for  captured  bleed  version  must  be  under  the 

installer’s discretion.

Note: Exhaust Port is nearer the conduit entry (LH side)

Enclosure Bleed Port is on the RH side. (See Figure 3.)

Figure 3 

Pneumatic Installation

These instruments are recommended for use with clean, dry, oil 

free instrument grade air to BS.6739 or ISA-7.0.01-1996.
Dew Point:   At  least  10°C  (18°F)  below  (-40°C)  minimum 

anticipated ambient temperature.

Dust: 

 

Filtered to below 50 microns.

Oil Content:  Not to exceed 1ppm mass.
The instrument is factory calibrated with a supply pressure of 30 

psig (2 bar) ±10%. Operation is possible at any pressure between 

18  and  150  psig  (1.3  to  10  bar),  though  recalibration  may  be 

necessary towards these limits to maintain specified accuracy.
The  inlet  and  outlet  ports  are  threaded  1/4"  NPT  female  and 

suitable fittings should be used. For most installations 1/4" (6mm) 

pipe will be adequate. If a large actuator, high flow rates or long 

pipework is necessary then a larger diameter should be used.
Plastic  tubing,  e.g.  Nylon  is  preferable  where  circumstances 

permit,  since  it  is  normally  very  clean  internally.  In  all  cases, 

purge the supply pipework before connection to the converter.
Two  gauge  ports  are  provided  to  facilitate  direct  mounting  of 

a pressure gauge. To use one of these ports remove the plug 

(using a 1/4" or 3/16" Hexagon Key) in a de-pressurized state, 

and connect the gauge. The ports are threaded 1/4" NPT at the 

back of the unit and 1/8" NPT at the front.

Exhaust Port

Enclosure Bleed Port

Содержание Masoneilan 4411 I.S.

Страница 1: ...Masoneilan 4411 Series Electropneumatic Transducer Instruction Manual Baker Hughes Data Classification Public...

Страница 2: ...CULAR REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE ME...

Страница 3: ...tured Bleed Version 3 Pneumatic Installation 3 Electrical Installation 4 Wiring and Cable Entry 4 Conduit Entry 4 Calibration 4 Tight Shut Off Adjustment Instructions 5 Simple Functional Checks 5 Tech...

Страница 4: ...ne Warranty Items sold by Baker Hughes are warranted to be free from defects in materials and workmanship for a period of one year from the date of shipment provided said items are used according to B...

Страница 5: ...rocess control applications The units operate a closed loop system incorporating a feedback sensor ensuring long term stability and high accuracy performance with fail safe operation i e the output fa...

Страница 6: ...be blocked with paint and or plastic sheeting etc Captured Bleed Version The baffles and the baffle cover are fitted to maintain the adequate Ingress Protection IP rating of the instrument Removal of...

Страница 7: ...conforming to explosion proof specifications must be used A ground terminal is provided both internally and externally and should be used if ground continuity is essential The unit is supplied with pl...

Страница 8: ...p pressure 0psi adjust potentiometer slowly clockwise until the output pressure falls to zero Do not turn the pot beyond this point The shut off point is now set Shut off point check Increase the inpu...

Страница 9: ...accordance with ANSI ISA 51 1 1993 N B Instrument accuracy excludes calibration errors Temperature Effect Span and Zero Mean temperature coefficient over full operating range 40 to 85 C less than 0 0...

Страница 10: ...III Division 2 Group FG T6 Ta 75 C T5 Ta 85 C CSA Class I Division 1 Group BCD Class II Group EFG Class III Ta 85 C T5 Ta 65 C T6 Class I Division 1 Group ABCD Class II Group EFG Class III Ta 85 C T4...

Страница 11: ...being adversely affected thus ensuring that the type of protection is not compromised Aggressive substances e g acidic liquids or gases that may attack metals or solvents that may affect polymeric ma...

Страница 12: ...9 Baker Hughes Copyright 2020 Baker Hughes Company All rights reserved...

Страница 13: ...Masoneilan Model 4411 Electropneumatic Transducer Instruction Manual 10 Copyright 2020 Baker Hughes Company All rights reserved...

Страница 14: ...11 Baker Hughes Copyright 2020 Baker Hughes Company All rights reserved Notes...

Страница 15: ...Masoneilan Model 4411 Electropneumatic Transducer Instruction Manual 12 Copyright 2020 Baker Hughes Company All rights reserved Notes...

Страница 16: ...ormation The Baker Hughes logo and Masoneilan are trademarks of Baker Hughes Company Other company names and product names used in this document are the registered trademarks or trademarks of their re...

Отзывы: