INSTALLATION
SETUP/INSTALLATION
I-E96-440A
2 - 7
The NKAS01 and NKAS11 are round, shielded cables that con-
nect the TU to the IMASI03 slave module. The NKAS01 cable
has a PVC jacket and is rated for 80 degrees celsius at 300 volt
(UL rated type CL2). The NKAS11 cable has a non-PVC jacket
and is rated for 90 degrees celsius at 300 volt (UL rated type
PLTC). See Figure
for the cable connections from the termi-
nation unit to the slave module. Table
lists the NTAI06
cable applications.
Figure 2-4. Installation for Revision A and B Hardware NTAI06
CAUTION
Remove modules (slave or termination) from their assigned
slots before installing a cable to that slot. Failure to do so
could result in damage to the module or station.
ATTENTION
Retirer les modules (asservi ou carte de raccordement) de leur
position assignée avant d'installer un câble à cette position.
Des dommages au module ou au poste pourraient résulter d'un
manquement à cette procédure.
CHASSIS COMMON
SCREW
TABS
STANDOFF
MOUNTING SCREWS
FIELD TERMINATION PANEL
T00592A