INTRODUCTION
INSTRUCTION CONTENT
I-E96-440A
1 - 3
•
Input channel transient and surge protection.
•
Analog input signal routing to the IMASI03.
•
Jumper configured input signal types:
System powered 4 to 20 mA inputs have individually fused
channels.
Field powered 4 to 20 mA.
Single ended voltage inputs have the minus input terminal
jumpered directly to I/O COM on the NTAI06.
Differential voltage inputs and three-wire RTDs have the
plus and minus and C terminals isolated with respect to
I/O COM and module common.
•
Source of the local cold junction reference for thermocouple
inputs.
•
Termination point for the shield of the NKAS01 or NKAS11
cable.
•
The termination unit can be located up to 60 meters
(200 feet) from the IMASI03.
INSTRUCTION CONTENT
This manual has five sections and an appendix.
Is an overview of the features, description and specifications
and a description of the NTAI06.
Describes cautions to observe when handling the TU. It shows
the steps to follow to install and connect the termination unit
before applying power. This section also presents jumper set-
tings.
Provides a maintenance schedule.
Details how to replace a TU.
Describes the support services (spare parts, training, docu-
mentation, etc.) available from Bailey Controls Company.
Shows the jumper settings, board layout and cabling for the
IMASI03 Universal Analog Slave Input Module.