INSTALLATION
INNIS01 NETWORK INTERFACE SLAVE MODULE CONFIGURATION
3 - 6
WBPEEUI250016A1
®
1
0
1
0
0
14
Number of transmitted message watchdog expirations.
1
0
1
0
1
15
Number of messages put into the receive buffer and
retained.
1
0
1
1
0
16
Number of bytes originated by this node (including retries).
1
0
1
1
1
17
Number of bytes received and forwarded by this node.
1
1
0
0
0
18
Number of I/O expander bus to NIS handshakes.
1
1
0
0
1
19
Number of I/O expander bus to transmit buffer signals.
1
1
0
1
0
1A
Number of I/O expander bus process control unit status
requests.
1
1
0
1
1
1B
Number of I/O expander bus NIS status requests.
1
1
1
0
0
1C
Number of I/O expander bus interrupts with invalid status.
1
1
1
0
1
1D
Number of transmit buffer realignments due to invalid
contents.
1
1
1
1
0
1E
Number of receive buffer realignments.
1
1
1
1
1
1F
Number of status buffer realignments.
User setting
NOTES:
1. 1 = OPEN or OFF, 0 = CLOSED or ON.
2. Shaded areas designate normal operating positions.
Table 3-5. INNIS01 Module Event Counters
(continued)
Dipswitch Pole
1
(Binary Value)
Hexadecimal
Value
Description
2
4
(16)
5
(8)
6
(4)
7
(2)
8
(1)
Table 3-6. INNIS01 Module Error Counters
Dipswitch Pole
(Binary Value)
Hexadecimal
Value
Description
4
(16)
5
(8)
6
(4)
7
(2)
8
(1)
0
0
0
0
1
01
Number of receive errors on loop 1.
0
0
0
1
0
02
Number of receive errors on loop 2.
0
0
0
1
1
03
Number of transmit errors for this node.
0
0
1
0
0
04
Number of messages lost to receive queue overflow.
0
0
1
0
1
05
Number of messages dumped with circulation count errors.
0
0
1
1
0
06
Number of dumped with destination count or message-type
errors.
0
0
1
1
1
07
Number of messages dumped with source-state errors.
0
1
0
0
0
08
Number of messages tempted with source-sequence
mismatch.
User setting