WIRING CONNECTIONS AND CABLING
The QRS has three card edge connectors to supply logic power,
establish slave expander bus communication and provide I/O
(P1, P2, P3 respectively).
Wiring
Installing the module in the MMU connects the slave module to
the logic power, necessary to drive the circuitry, at P1. It will
also connect P2 to the slave expander bus for communication
with the MFP. P1 and P2 connections require no additional wir-
ing or cabling.
NOTE: You must install a dipshunt on the backplane of the MMU to
connect the slave expander bus between the slave module and
master module. Locate the modules so the bus can connect the
modules or they will not communicate.
Cable Connections
The IMQRS02 uses either an NTCS02 or NICS01 for termina-
tion. See Figure
to determine the cables to use with the ter-
mination unit or module you are using.
Figure 3-5. IMQRS02 Cable Connections and Termination
TP27144A
P1
P1
P3
P1
P3
P1
P2
P2
NKTM01
OR
NKTU02
NICS01
IMQRS02
NTCS02
IMQRS02
NKTU01
4 ANALOG INPUTS
(1-5 VDC, 4-20 mA)
3 DIGITAL INPUTS
(24/125 VDC, 120 VAC)
4 ANALOG INPUTS
(1-5 VDC, 4-20 mA)
3 DIGITAL INPUTS
(24/125 VDC, 120 VAC)
2 ANALOG OUTPUTS
(1-5 VDC, 4-20 mA)
4 DIGITAL OUTPUTS
(24 VDC AT 250 mA)
2 ANALOG OUTPUTS
(1-5 VDC, 4-20 mA)
4 DIGITAL OUTPUTS
(24 VDC AT 250 mA)