INSTALLATION
SETUP/PHYSICAL INSTALLATION
3 - 4
I-E96-316A
®
ing a
time-out
if the
hold
option is selected; they change to the
power up
values (0 or 100 percent) if the
go to power up state
is
selected. Position 2 selects the
time-out
option for AO1. Position 5
selects the
time-out
option for AO2.
explains the bus
fault timer in more detail.
Switch positions 1 and 4 are not used and should be in the
closed position. Figure
shows the analog output default
switch (S2); refer to Table
for the switch settings. Deter-
mine the requirements for your process and set the
dipswitches to the positions shown in the table.
Analog Output Mode Switch (S3)
The analog output mode switch (S3), shown in Figure
selects the mode or type of each analog output. The mode can
be set to current (4 to 20 mA) or voltage (1 to 5 VDC).
Set the switch to position C1 for a current output at AO1 or
position C2 for a voltage output at AO1. Set the switch to posi-
tion C3 for a current output at AO2 or position C4 for a voltage
output at AO2. Figure
shows the analog output mode
switch (S3). Refer to Table
for the switch settings.
Figure 3-3. Analog Output Default
Switch (S2)
Table 3-2. Analog Output Default Switch (S2) Settings
Analog
Output
Time-Out Option
Power Up State
Switch
Go To
Power Up
Hold
Switch
0%
100%
1
2
CLOSED
OPEN
3
CLOSED OPEN
2
5
CLOSED
OPEN
6
CLOSED OPEN
1
2
3
4
5
6
OPEN
NOT
USED
NOT
USED
ANALOG
OUTPUT 1
ANALOG
OUTPUT 2
TP27112A