INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-316A
3 - 5
Digital Input Jumper Settings
Jumpers J-1 through J-3 set the input voltage levels and
jumpers J-4 through J-6 set the DC voltage response time. The
DC inputs have two propagation (speed) choices: a slow setting
(17 millisecond response time) or fast setting (1.5 millisecond
response time). There are four terminals at each of these
jumper locations. Refer to Table
to determine the jumper
settings for your application; place a jumper across the pins
shown in the table. Figure
shows the location of the jump-
ers on the IMQRS02.
NOTE: J-7 is a clock jumper used for factory testing. The jumper is
installed at the factory and must remain in place; DO NOT remove it.
Removing it will cause the module to operate erratically.
Figure 3-4. Analog Output Mode
Switch (S3)
Table 3-3. Analog Output Mode
Switch (S3) Settings
Analog
Output
Switch Position
Current
Mode
Voltage
Mode
1
C1
C2
2
C3
C4
C1
C2
C3
C4
ANALOG
OUTPUT 1
ANALOG
OUTPUT 2
TP27105A
Table 3-4. Digital Input Jumper Settings
Digital
Input
Jumper (J) 120 VAC
125 VDC
Slow
125 VDC
Fast
24 VDC
Slow
24 VDC
Fast
1
1
4
1-2
1-2
2-3
2-3
2-3
3-4
3-4
2-3
3-4
3-4
2
2
5
1-2
1-2
2-3
2-3
2-3
3-4
3-4
2-3
3-4
3-4
3
3
6
1-2
1-2
2-3
2-3
2-3
3-4
3-4
2-3
3-4
3-4