INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-215A
3 - 3
SWITCH S2 AND S3 SETTINGS
Switches S2 and S3 set the analog output type and default
value (the value of the output during power up, reset and cer-
tain failure conditions) for analog output number 1 and 2
respectively. Figure
shows the location of S2 and S3. Table
shows the selectable options and the corresponding
dipswitch settings. Each dipswitch position (position 1) or
group of positions (positions 2, 3 and 4 through 6) functions
independently of each other. Please note that the dipswitch
settings in Table
apply to both S2 and S3.
WARNING
The control system must be carefully evaluated to establish
default values that will prevent personal injury and/or property
damage in the case of module failure.
AVERTISSEMENT
Il faut soigneusement évaluer le système de commande afin
d'établir des valeurs par défaut qui permettront d'éviter des
blessures et des dommages matériels en cas de défaillance
des modules.
CAUTION
Do not set switch S2 and S3 to any configuration other than
those specified in Table 3-1. Damage to the circuit board may
result.
ATTENTION
Le réglage des interrupteurs S2 et S3 doit correpondre à l'un
des choix figurant au Tableau 3-1. Sinon, la carte de circuits
imprimés pourrait être endommagée.
Table 3-1. Switch S2 and S3 Settings
Position
Setting
Function
User Setting
1
1
0
5.25 VDC analog output during power up.
0.75 VDC analog output during power up.
2
3
1
0
0
1
Holds last analog output value on timeout.
Goes to power up value set by S2-1 on timeout.
4
5
6
0
1
0
1
0
1
Yields voltage output (1 to 5 VDC).
Yields current output (4 to 20 mADC).
NOTE: 1=OPEN (OFF); 0=CLOSED (ON)