DESCRIPTION AND OPERATION
I-E96-225A
2 - 5
Dipswitches
•
Each dipswitch has eight poles.
•
Dipswitch SW2 sets module options.
•
Dipswitch SW3 sets the module address.
•
A reset switch (SW1) accessed through the faceplate resets
the module.
Jumpers
•
Jumpers J1 through J3 enable handshake functions for
the EWS port.
•
Jumper J4 connects the EWS connector cable shield to
ground.
•
Jumper array J5 selects DTE, DCE or loopback operating
mode for the DB-25 EWS port (P4).
•
Jumper array J6 selects DTE, DCE, or loopback operating
mode for the DB-9 connector mounted on the circuit board.
•
Jumper J11 allows the CTT terminal to communicate on
Controlway or module bus under IMCPM03 module con-
trol. Jumper J11 must always be set shorting pin 2 to pin 3
to ensure correct operation of the IMCPM03 module and
the CTT terminal.
•
Jumper J12 disconnects -30 VDC from the module when
installing it in an MMU backplane with modules that
require -30 VDC. The Controlway can not be used in sys-
tems that use -30 VDC.