INSTALLATION
I-E96-225A
3 - 13
6. Before installing the module, check all dipswitch and
jumper settings, and ensure that respective module cables are
attached to the MMU backplane.
The IMCPM03 module can be installed and removed under
power. Installing the module with power applied causes the
status LED to turn red momentarily and then turn green. If it
does not, refer to
To install module:
1. Guide the top and bottom edges along the top and bottom
rails of the MMU backplane.
2. Slide the module into the slot. Push it until the rear edge is
firmly seated in the backplane connectors.
3. Turn the two concentric screws ½-turn clockwise to lock
the modules in place.
INSTALLING THE TERMINATION UNIT OR MODULE
For permanent mounting, the IMCPM03 module can connect
to a termination unit or termination module. Refer to
and
for information about these termi-
nation devices.
CAUTION
It is strongly recommended that all power (cabinet, I/O, etc.) be
turned off before doing any wiring. Verify all connections
before applying power. Failure to observe these precautions
could result in equipment damage. Do not apply power to the
termination unit when uncut dipshunts are installed. This may
result in damage to the termination unit.
Verify that all termination unit dipshunts are configured before
applying power. Failure to do so may result in damage to the
termination unit.
ATTENTION
Il est fortement recommandé de débrancher toute source d'ali-
mentation (armoire, E/S, etc.) avant d'effectuer du travail au
câblage. Vérifiez toutes les connexions avant de rétablir l'ali-
mentation. Ces précautions permettent d'éviter des dommages
a l'équipement.
S’assure que tous les dipshunts de la carte de raccordment
sont configurés avant de mettre sous tension. Un dommage à
la carte de raccordement peut être causé si on ne prend pas
cette précaution.