INTRODUCTION
I-E96-221A
7 - 1
SECTION 7 - REPAIR/REPLACEMENT PROCEDURES
INTRODUCTION
Repair procedures are limited to module replacement. If the
IMCPM02 module fails, remove and replace it with another.
Verify that firmware revision levels match and that replace-
ment switch settings are the same as the failed module. Refer
to Table
for a list of recommended spare parts.
MODULE REPLACEMENT
Follow Steps 1 through 5 to replace the IMCPM02 module.
NOTE: The IMCPM02 module can be removed when power is
applied.
1. Turn the two concentric screws ½ turn either way to
release them.
2. Grasp the screws and slide the module out.
3. Set switches SW1 and SW2 on the replacement to match
the settings of the CPM module recently removed.
4. Verify jumpers J5 and J6, and J11 and J12.
5. Hold the module by the faceplate and slide it into the slot;
push until the rear edges are firmly seated in the backplane
connectors.
6. Turn the two concentric screws ½ turn clockwise either
way to lock the module into the module mounting unit.
Table 7-1. Recommended Spare Parts List
Description
Part Number
Quantity
Module, communication port module
IMCPM02
1
Termination module, multi-function processor
NIMP01
1
Termination unit, multi-function processor
NTMP01
1
Cable, IMCPM02 to termination unit
NKTU01
1
Cable, IMCPM02 to termination module
NKTU02
1