TROUBLESHOOTING
MODULE PIN OUT
I-E96-206A
5 - 3
Incorrect Address
Verify that FC 28 in a master module directing an AOM output
is correct. Specification 1 (S1) of this FC is the AOM address.
Make sure that it is the same as the address set on the AOM
address switch. If not:
1. Remove the module and change the setting of the address
switch to correspond with the master module configuration
(refer to
for the procedures to set an address and to
install the module).
OR
2. Modify the address in the master module configuration (FC
28 S1) to correspond with the address set on the address
switch. Use an INFI 90 operator interface to modify the config-
uration (for procedures on how to modify a function code spec-
ification, refer to the Product Instruction for the operator
interface you are using).
Incorrect Block
Number
Each FC 28 defines only one output. To output a signal from
an output channel, specification 2 (S2) must be set to that out-
put channel number (1 to 8). If an output signal is not present
at a channel that should have an output, verify that a FC is
configured with that output channel specified in S2.
OUTPUT CIRCUIT ERROR
If all inputs to an AOM are correct and the outputs are still not
correct, this may indicate a module output circuit failure.
Replace the AOM or contact your nearest Bailey Controls rep-
resentative.
MODULE PIN OUT
The module has two connection points for external signals and
power (P1 and P3). Tables
show the pin connec-
tions.
Table 5-3. P1 Pin Connections
Pin
Connection
Pin
Connection
1
2
3
4
5
6
+5 VDC
+5 VDC
NC
NC
Common
Common
7
8
9
10
11
12
NC
NC
PFI
PFI
Module bus
Module bus
PFI=Power Fail Interrupt
NC=Not Connected