INSTALLATION
SETUP/PHYSICAL INSTALLATION
3 - 2
I-E96-206A
®
SETUP/PHYSICAL INSTALLATION
The address dipswitch (S2) must be set, and the analog output
jumpers (E3, E6 thru E13) configured
BEFORE
installing or
operating the AOM. Its respective Termination Unit (TU) or Ter-
mination Module (TM) must be configured to develop the cor-
rect analog signals from the AOM.
NOTES:
1.
Jumpers E1 and E2 are factory installed and must NOT be
changed or removed. The type of PROM used determines the
jumper settings. Removing or changing the jumpers will cause the
module to operate incorrectly.
2.
R25 is set during factory calibration of the module; DO NOT
adjust it. Adjusting R25 will cause incorrect voltage or current outputs.
Address Switch (S2) Setting
The AOM can have one of 32 addresses (0 to 31) on the module
bus. This address uniquely identifies the AOM to a master
module or operator interface. Function Code (FC) 28 specifica-
tion 1 in a master module configuration must be the same as
the address on S2 of an AOM to direct output signal values to
that AOM.
NOTE: The address must be a unique address within a PCU. Nor-
mally, addresses 0 and 1 are not used for an AOM since these are
reserved for communication modules.
The module address is set by positioning the five dipswitches
on S2; Figure
shows the location. Table
is a binary
address conversion table for setting S2.
Figure 3-1. Analog Slave Output Module
MODULE STATUS LED
ADDRESS SWITCH
MODULE RESET
SWITCH
OUTPUT VOLTAGE
RANGE JUMPER
OUTPUT MODE
JUMPERS
TP27212A
1
5
OPEN
S2
P1
P3
EDGE
CONNECTORS
E2
1
2
3
E6
1 2 3
E7
1 2 3
E12
1 2 3
E11
1 2 3
E10
1 2 3
E9
1 2 3
E8
1 2 3
E13
1 2 3
E3
1
2
3
E1
1
2