![Bailey infi 90 IISAC01 Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/bailey/infi-90-iisac01/infi-90-iisac01_instruction_3456674038.webp)
DESCRIPTION AND OPERATION
SAC STATION I/O CIRCUITRY
I-E96-117B
2 - 19
to five VDC level. An on-board analog to digital converter (ADC)
translates this zero to five VDC signal to a digital value.
Analog input two has a square root display option. When
enabled (dipswitch SW4, position one), it takes the square root
of the zero to 100 percent input signal. This signal is then mul-
tiplied by a gain of ten for a new zero to 100 percent value. This
signal conditioning is only used by the station for display
purposes.