INSTALLATION
INSTALLING THE TERMINATION UNIT OR MODULE
3 - 8
I-E96-202B
®
Controlway Cable
Install the Controlway or module bus cable in INFI 90 module
mounting units as follows:
1. Attach one end of the Controlway or module bus cable
(twisted 3-wire) to the bottom three tabs on the lower left of the
module mounting unit backplane (facing from behind). See Fig-
ure
.
2. Attach (in the same sequence) the other end of the cable to
the bottom three tabs on the lower left of the next module
mounting unit backplane.
NOTE: Due to high speed constraints, a maximum of eight related
(Controlways linked by cable) module mounting units can be
installed in one cabinet. The number of interconnected module
mounting units (Controlway or module bus) should be kept to a min-
imum to avoid crosstalk and interference. You cannot cable link
Controlways in separate cabinets.
INSTALLING THE TERMINATION UNIT OR MODULE
Refer to the NTMP01 termination unit product instruction or
the NIMP01 and NIMP02 termination module product instruc-
tion for information about how to install and connect commu-
nication and power wiring to these termination devices. The
following is a general introduction to termination unit or mod-
ule installation.
NTMP01 Termination Unit Installation
1. Configure the jumpers on the termination unit. Refer to
for quick reference or to the appropriate instruction
for detailed information on jumper settings and applications.
Figure 3-2. Controlway Cable Installation
TP 5 0 3 2 0 A