COMPONENT DESCRIPTION AND REPLACEMENT
CONSOLE POWER ENTRY PANEL REMOVAL
WBPEEUI220760A0
6 - 19
CONSOLE POWER ENTRY PANEL REMOVAL
To remove the power entry panel from an IIOIS43 console refer
to Figure
1. Turn off the main circuit breaker on the power entry panel.
Check the power indicator to see if power is removed.
2. Shut down AC line power to cabinet (plant breaker) so that
the AC line may be disconnected safely.
3. Remove all cables from the front of the power entry panel
(RS-232-C, SCSI, alarm contact wires and AC input).
4. Remove AC cables from the outlets on the power entry
panel.
5. Remove all signal cables from the multibus modules that
go to the rear of the power entry panel. Leave the cables on the
power entry panel. The new power entry panel comes with
cables.
6. Remove the five screws from around the front of the power
entry panel. Slide the power entry panel out the front of the
cabinet.
Figure 6-12. Console Power Entry Panel (PEP) Removal
F R O N T VIEW
P O W E R E N T R Y
PA N E L M O U N T IN G
S C R E W S (5 )
C P U
T P 3 6 1 63 B