background image

Installation and operation manual 

 Version RCM-10/03-e 

Programming Page 

11/18 

 
 
 
 

7.2.1  4-20 mA span adj 

 

At this point you can adjust the 4-20 mA output span. 
Use a calibrated 41/2 digit DMM set for 199.99 mA 
range and attach the test leads to TB2 pins 19 and 
21. Use the up and right arrow keys to change the 
span value on line 2. Monitor the current indication 
until the current is set for 20.00 +-.001. Then press 
the enter key to store the span value and proceed to 
the next menu. 

 

7.2.2  4.20 mA zero adj 

 

The 4-20 mA output zero can now be adjusted. Use a 
calibrated 41/2 digit DMM set for 19.999 mA range 
and attach the test leads to TB2 pins 19 and 21. Use 
the up and right arrow keys to change the zero value 
on line 2. Monitor the current indication until the 
current is set for 4.00 +-.001. Then press the enter 
key to store the zero value and proceed to the next 
menu. 

 

7.2.3  Programming set point 

 

The next menu selection is the set point adjustment. 
Use the up arrow to move the > prompt to the 
change location on the screen, then press the right 
arrow key to select the next menu. 
 
 
Use the up or right arrow to adjust the set point value 
from a value ranging from 0 to 100%. To save the 
value, press the Enter key. This action will 
automatically move to the next menu. 

 

7.2.4 Resetting 

totalizer 

 
The next menu selection is the totalizer reset. Use 
the up arrow to move the > prompt to the change 
location on the screen, then press the right arrow key 
to select the next menu. 
 
 
Use the up arrow to clear the totalizer to zero. To 
move on to the next menu press the Enter key 

 
 

Содержание RCM 2000

Страница 1: ...Badger Meter Europa GmbH Model RCM 2000 Research Control MAG meter Low flow magnetic flow meter INSTALLATION AND OPERATION MANUAL September 2004 Version RCM 09 04 e...

Страница 2: ...1 1 Menu structure 10 7 1 2 Pushbutton key function 10 7 2 User output programming 10 7 2 1 4 20 mA span adj 11 7 2 2 4 20 mA zero adj 11 7 2 3 Programming set point 11 7 2 4 Resetting totalizer 11 7...

Страница 3: ...trained by the operating authority and the instructions of this manual have to be followed Principally the regulations for the opening and repairing of electrical equipment in your country have to be...

Страница 4: ...s manual where the changes have occurred 3 Unpacking inspection 1 If damage to the shipping container is evident upon receipt request the carrier to be present when the product is unpacked 2 If damage...

Страница 5: ...tory and will have the same serial numbers When replacing the detector there is a configuration file that can be downloaded through the front panel RS 232 serial port for simple setup Install RCM flow...

Страница 6: ...rdance with local codes Green GND White LO neutral Black HI hot For power spikes a replaceable fuse is located on the board just above AC power terminal It is a 240 Volt 0 25 amp 5mm fuse 5 2 Sensor u...

Страница 7: ...pe output 11 Option out collector 12 Empty pipe input 13 Option out emitter 14 Preamp 9VDC power White 31 15 Frequency out collector 16 Preamp 9VDC power Green 30 17 Frequency out emitter 18 Preamp pr...

Страница 8: ...umpers removed the outputs are open collector and are capable of switching 30 VDC 50 mA This type of output is duplicated for the totalizer set point and optional outputs J1 J2 J3 J4 J5 J6 Totalizer 0...

Страница 9: ...e coils are energized a magnetic field is created across the whole diameter of the tube When a conductive fluid flows through this magnetic field a voltage is induced across the electrodes based upon...

Страница 10: ...firmware revision Normal flow measurement screen shows rate velocity totalization and system status 6 1 1 Rate The current flow rate in the programmed units The flow units available are Gallons per mi...

Страница 11: ...ing attach a jumper wire between terminal TB2 19 and TB2 21 LC Low flow cutoff No action should be needed unless you have the low flow cutoff set below where the user wants it The factory default is 2...

Страница 12: ...er The Enter key allows you access the next menu or to store programming values When entering numerical values a flashing cursor appears on the number to be changed The programming parameter is change...

Страница 13: ...ys to change the zero value on line 2 Monitor the current indication until the current is set for 4 00 001 Then press the enter key to store the zero value and proceed to the next menu 7 2 3 Programmi...

Страница 14: ...e number will range between 20 to 70 To save the value press the Enter key This action will automatically move to the next menu 7 2 6 LCD backlight enable The next menu selection is the LCD backlighti...

Страница 15: ...hether they are metric mps or English fps To save the units press the Enter key This action will automatically move to the next menu Note When changing units remember to check the full scale flow and...

Страница 16: ...ompt to the change location on the screen then press the right arrow key to select the next menu Use the up or right arrow to adjust the number of pulses per unit volume The units have been automatica...

Страница 17: ...ust the response between slow medium and fast Use the fast setting for velocities 2 fps and applications that have low flow noise and require quick batching Use the medium setting for normal applicati...

Страница 18: ...e Coil cable 2 conductor common shield foil shield or braid shield AWG 18 to22 e g Belden cable 9462 9962 8760 22 AWG 20AWG 18AWG Sensor cable 4 conductors 2 conductor foil shield 2 conductor unshield...

Страница 19: ...n system and I O status Programming Front panel accessible 3 pushbuttons Power 85 240 VAC 50 60 Hz fuse rating 0 1A or 24 VDC 200 mA continuous 5 Watt power dissipation Accuracy Standard 5 of reading...

Страница 20: ...form us about possible medium wastes remaining in the part For this purpose please use this form A security specification sheet of the medium must accompany this declaration in the following cases Tox...

Страница 21: ...Hotline Tel 49 7025 9208 0 or 30 Fax 49 7025 9208 14 Badger Meter Europa GmbH Subsidiary of Badger Meter Inc USA Karlstrasse 11 72660 Beuren Germany E mail badger badgermeter de www badgermeter de...

Отзывы: