Programming
Page 30/51
MID_M2000_BA_02_1807
5.2.6 Advanced
Datalogger
Note: For this feature is a special memory card necessary (blue memory
token) which will pluged in into a memory slot on the main board. This
is optional and will be not delivered with the common product.
First adjust the system clock before programing the interval time
otherwise the data logging records have the wrong time stamps.
Once the system clock is configured, ensure the supplied memory
token is inserted into the meter before configuring the Data Logging
interval time. Configuring the interval time will format the memory
token (when necessary) and assign it to the meter. This formating
process can take approximately 30 seconds. A flash screen indicates if
the token is being formatted.
Note: Placing this token after it has been formatted into an alternate
meter will reformat the token and all previously logged data will be lost.
All logged events can be extracted from the meter using the supplied
flow meter tool software, which connects the laptop to the meter via
the supplied RS232 cable.
The Data Logging feature records three types of events to a
memory token:
•
Totalizer/error events
•
Configuration change events
•
Startup events (power up, power down or reset events)
Up to 10.000 totalizations, 768 configuration and start up events can
be recorded.
Logging
Interval
The table below defines the capacity of the memory
token:
•
15 minutes
(104 days)
•
1 hour
(1 year / 51 days)
•
12 hours
(13 years)
•
24 hours
(27 years)
Over time the data logging will reach capacity of the
memory token. Any new event to be recorded will
overwrite the oldest event on record.
View System
clock
Display internal system clock (24-hour mode) with
following format:
TT/MM/JJ
HH/MM/SS
Set System
clock
Configure the internal system clock using 24-hour
format:
TT/MM/JJ
HH/MM/SS
Token Copy
Note: For this feature is a special memory card necessary (red memory
token) which will pluged in into a memory slot on the main board. This
is optional and will be not delivered with the common product.