4.8 Diagnostics
71 DIAGNOSTICS = dIA 7 (diagnostic mode) dIA7
a) Press and hold down RESET for 5 seconds until “MEtr 1” appears.
71 DIAGNOSTICS = dIA 7 (diagnostic mode)
b) Press the DISP button 6 times to reach “dIA 7”.
c) Press RESET “dIA 71” will appear.
d) Press and hold down RESET for 2 seconds.
(Program will appear then all the segments should be displayed).
e) Press the DISP button “diSP” (to check that the display button is working properly).
f) Press the RESET button “RESEt” (to check that the reset button is working
properly).
g) Press and hold down RESET for 2 seconds. Program will disappear (check the
condition of the reed switch).
Note: The condition of the reed switch can only be checked when there is liquid
flowing through the meter. The reed switch should be reading between 50 - 80.
h) Press RESET for five seconds to return the meter to the operating mode.
Trouble shooting guide
TROUBLE CAUSE
REMEDY
Register not
visible
a) Low battery voltage
a) Replace batteries
b) LCD sun damaged
b) Replace register assembly, protect
LCD from direct sunlight
Register visible
but not reading
flow
a) Faulty reed switch connection
a) Check connection into meter
terminal block
b) Reed switch faulty
b) Replace reed switch - refer to
meter manual
Meter
inaccurate
a) Incorrect k-factor
a) Correct k-factor, contact local
distributor for details if required
b) Display units set incorrectly
b) Check display units and correct if
necessary
Specifications
Battery type:
2 x AAA Alkaline
Batch:
999999 (ltr, qts or gal etc.)
Resettable totalizer:
999999 (ltr, qts or gal etc.)
Non-resettable totalizer:
999999 (ltr, qts or gal etc.)
Input device:
Reed switch only
Display units:
BBL, Ton, Tonne, M^3, kg, gm, Lb, OZ, Gl, Qt, Pt, Lt, none
Rate units:
sec, MIN, HR
Maximum temperature:
55°C (131°F)
Minimum temperature:
-5°C (23°F)