PROGRAMMING

OTEE:

N

All of the following parameters appear in 

Extended Programming

 mode  Parameters with an asterisk (*) appear in 

Programming

 mode as well 

Parameters

Select Display Function

The ER-500 monitor has three display selections— 

Flow

Grand Total

 and 

Test

 

Flow

Use the 

Flow

 setting for normal operation of the monitor  In this mode, the display shows both the instantaneous flow rate 

and current total simultaneously, see 

Figure 6

 

2

1

Current Total Units

Flow Rate

Units

Totalizer

Multiplier

Current

Total

Instantaneous

Flow Rate

Figure 6:  Instantaneous flow rate and current total

Flow Grand Total

The 

Flow-GT

 setting forces the meter to alternate between the instantaneous flow and the grand total with roll-over counts, 

see 

Figure 7

 

The grand total is the accumulation of all the fluid that has gone through the meter since the last time the grand total was 

cleared  This totalizer is in addition to the current total totalizer on the display and is always enabled 
In addition, the grand total screen displays the number of times the grand total has reached its maximum count (9,999,999) 

and rolled over to zero  

2

1

Roll-over

Indicator

Totalizer

Mode

Total

Roll-Overs

Figure 7:  Grand total

Test

The 

Test

 setting places the monitor into a special diagnostic mode that shows the current input frequency and the 

accumulated input counts  

Figure 8

 shows the layout for test mode values  The diagnostic mode makes it possible for you to 

see precisely the frequency input the monitor is seeing and is very useful in troubleshooting and electrical noise detection 
At the 

Display

 prompt, press 

ENTER

 to view the current display setting  If the current display setting is correct, press 

ENTER

 to 

advance to the next parameter  To change the display setting, press 

UP

 or 

RIGHT

 to scroll through the display options  Press 

ENTER

 to save and advance to the 

KFacUnit

 parameter 

2

1

Input

Frequency

Totalizer

Counts

Figure 8:  Test mode screen

Programming

DSY-PM-00028-EN-02

Page 16 

February 2017

Содержание ER-500

Страница 1: ...Display ER 500 Advanced DSY PM 00028 EN 02 February 2017 Programming Manual...

Страница 2: ...ER 500 Flow Monitor Page ii February 2017 DSY PM 00028 EN 02...

Страница 3: ...9 Programming Using Frequency Output Flow Sensors 9 Menu Structure 10 Standard ER 500 Rate SU is Set to Simple 10 Advanced ER 500 Basic Menu 11 Standard ER 500 Rate SU is Set to Advanced 12 Advanced E...

Страница 4: ...ER 500 Flow Monitor Page iv February 2017 DSY PM 00028 EN 02...

Страница 5: ...avoided could result in severe personal injury or death Indicates a hazardous situation which if not avoided is estimated to be capable of causing minor or moderate personal injury or damage to proper...

Страница 6: ...a frequency output The output signal for these type of sensors is a frequency proportional to the rate of flow The ER 500 monitor uses the frequency information to calculate flow rate and total flow...

Страница 7: ...e that came with the IOG meter For instructions on programming the K factor see Enter Flow Sensor s K factor on page 17 Transmitter Connections The ILR transmitter typically used with the IOG meter fa...

Страница 8: ...he current loop is used a sensing circuit within the monitor detects the presence of the current loop and automatically disconnects the battery from the circuit JP1 JP2 JP3 Input Total Pulse Signal P1...

Страница 9: ...hen the grand total Modes RUN Normal operating mode PROGRAM Used to program parameters in the display EXTENDED PROGRAMMING Used to program advanced variables into the display TEST Used as a diagnostic...

Страница 10: ...ape Key Rate SU Rate Unit Setup Simple Advanced Flo Unt Rate Total Units GPM Gal OB D BBL m D m m H m LPM Ltr Gallons Min Gallons Oil Barrel Day Barrels Meters Day Meters Meters Hour Meters Liters Min...

Страница 11: ...rs T Meters T Feet T Million Gallons T Kilograms T Pounds T MASS TotalUnt Totalizer Unit Gal LBL OBL AFt MLt LPT m Ft MGa Kgs Lbs Gallons Liquor Barrel Oil Barrel Acre Feet Million Liters Liters Meter...

Страница 12: ...rel T Oil Barrel T Acre Feet T Million Liters T Liters T Meters T Feet T Million Gallons T Kilograms T Pounds T MASS TotalUnt Totalizer Unit Gal LBL OBL AFt MLt LPT m Ft MGa Kgs Lbs Gallons Liquor Bar...

Страница 13: ...Output Numeric Entry 4 20Tst 4 20 mA Output Numeric Entry Numeric Entry Numeric Entry Coef 1 Coefficient 1 Numeric Entry Freq x Frequency 2 10 Numeric Entry Coef x Coefficent 2 10 Numeric Entry NO YE...

Страница 14: ...t T Million Liters T Liters T Meters T Feet T Million Gallons T Kilograms T Pounds T MASS TotalUnt Totalizer Unit Gal LBL OBL AFt MLt LPT m Ft MGa Kgs Lbs Gallons Liquor Barrel Oil Barrel Acre Feet Mi...

Страница 15: ...e Output Disable Enable Numeric Entry Fl 20mA Flow at 20 mA Continued from previous page Modbus Address 1 to127 BusAddr Clr G T Clear Grand Total Passwd Password Modbus Disable Enable Numeric Entry Se...

Страница 16: ...in addition to the current total totalizer on the display and is always enabled In addition the grand total screen displays the number of times the grand total has reached its maximum count 9 999 999...

Страница 17: ...ompt press ENTER The monitor flashes the current total units If the current selection is correct press ENTER to advance to the next parameter To change to an alternate unit press UP or RIGHT to scroll...

Страница 18: ...Cutoff parameter NOTE N If the number you enter is out of range the display flashes Limit and refuses the entry Low Flow Cutoff The flow cutoff shows low flow rates that can be present when pumps are...

Страница 19: ...oint 2 Gnd Total Reset Total Pluse Signal Gnd Mag Pulse Iso OC Low High Input Total Pulse Signal TB1 Open Drain FET Total Pulse Output 2 2 10K Pull up Resistor VCC Internal 100 mA Maximum Figure 9 Ope...

Страница 20: ...tment To set the 4mA Out value connect an ammeter in series with the loop power supply as shown in Figure 11 The 4 mA DAC setting is typically 35 50 At the 4mA Out prompt press UP to increase or RIGHT...

Страница 21: ...ance to the Coef 1 parameter Coefficient The coefficient is the value applied to the nominal K factor to correct it to the exact K factor for that point The coefficient is calculated by dividing the a...

Страница 22: ...nt the display digit until it matches the first digit of the new bus address Press RIGHT to advance to the next digit Repeat for all digits of the address Press ENTER to save the new address and advan...

Страница 23: ...transistor reacts around a setpoint by taking recent history into account Hysteresis prevents an output from turning on and off rapidly when the programmed flow rate is at or very near the setpoint Fo...

Страница 24: ...um Flow Output ON O F F 8 g p m S e t p o i n t 1 0 g p m Hysteresis 2 gpm Output OFF Figure 15 Setpoint example At the TripSP1 prompt press ENTER The tripping condition setting is displayed If the cu...

Страница 25: ...ulses when the count total reached 1000 you would have accumulated 1 gallon of liquid Using the same reasoning each individual pulse represents an accumulation of 1 1000 of a gallon This relationship...

Страница 26: ...values are Velocity 4 3 ft sec Inside Diameter of Pipe 3 068 in Find the area of the pipe cross section 2 3 068 2 Area r2 Area x 2 35 7 39 in2 Find the volume in 1 ft of travel 88 71in2 7 3 in2 x 12...

Страница 27: ...which order the words are sent as long as the receiving device knows which way to expect it Since word order is a common problem between devices many Modbus master devices have a configuration setting...

Страница 28: ...the OFF state 3 8 Spares Alarm Setpoint 1 9 0 Setpoint OFF 1 Setpoint ON Alarm Setpoint 2 10 0 Setpoint OFF 1 Setpoint ON 11 16 Spares Opcode 01 Read Coil Status This opcode returns the state of the...

Страница 29: ...ess the tab on the battery connector to release it from the circuit board see Figure 18 Freq In 4 20mA Iso Total Pluse TR_B TR_A RS485 Gnd Setpoint 1 Setpoint 2 Gnd Total Reset OC Total Pluse Signal G...

Страница 30: ...sistor Adjustable flow rate with programmable dead band and phase Maximum Voltage 28V DC Maximum Current 100 mA Pull Up Resistor External required 2 2 K ohm minimum 10 K ohm maximum Modbus Advanced On...

Страница 31: ...voltage is checked across or in parallel with the 4 20 mA terminals and current is checked with the ammeter in series with the 4 20 mA output No Rate or Total Displayed Check connection from meter s t...

Страница 32: ...ENTRIE THROUGH SUITA STRAIGHT THRU 5 WHEN SELECTING CABLE FOR CONNECTION TO TURBINE METER USE CABLE WITH THE FOLLOWING HAZARDOUS LOCATION 10 FT TO MAX 100 FT HAZARDOUS LOCATION CLASSIFIED CLASS I DIV...

Страница 33: ...THROUGH SUITABLY SIZED UL CSA CERTIFIED LIQUID TIGHT STRAIGHT THRU FITTINGS NOTES ON FLOW SENSOR 1 INTERCONNECTING CABLE CAPACITANCE AND INDUCTANCE PLUS THE CAPACITANCE AND INDUCTANCE OF THE MAGNETIC...

Страница 34: ...Display ER 500 Advanced INTENTIONAL BLANK PAGE DSY PM 00028 EN 02 Page 34 February 2017...

Страница 35: ...Programming Manual INTENTIONAL BLANK PAGE DSY PM 00028 EN 02 Page 35 February 2017...

Страница 36: ...2 55 5662 0882 Europe Middle East and Africa Badger Meter Europa GmbH Nurtinger Str 76 72639 Neuffen Germany 49 7025 9208 0 Europe Middle East Branch Office Badger Meter Europe PO Box 341442 Dubai Sil...

Отзывы: