background image

Select Display's K-factor Unit*

At the 

KFacUnt

 prompt, press 

ENTER

  The display shows the current K-factor unit  If the current selection is correct, press 

ENTER

 to advance to the next parameter  To change the K-factor unit, press 

UP

 or 

RIGHT

 to scroll to the correct unit  The units 

should match the units that the meter was calibrated in  Press 

ENTER

 to save and advance to the 

KFactor

 parameter 

Enter Flow Sensor's K-factor*

OTEE:

N

The K-factor supplied with your meter or calculated from calibration data is needed to complete this step 

At the 

KFactor

 prompt, press 

ENTER

  The most significant digit in the K-factor flashes  If the current K-factor is correct, press 

ENTER

 to advance to the next parameter  To change the K-factor, press 

UP

 

to increment the digit until it matches the meter’s 

first K-factor digit  Press 

RIGHT

 to advance to the next digit  Repeat this process until all K-factor digits have been entered  

Press 

ENTER

 to save the K-factor and advance to the 

RateInt

 parameter 

OTEE:

N

The number of digits available before and after the decimal point is determined by the bore size of the flow sensor 

being used  The largest K-factors are associated with the smallest bore sizes  The maximum allowable K-factor is 

99999 9  The minimum must be at least 1 000  If an out-of-range number is entered, the display flashes 

Limit

 and 

refuses the entry 

Select Rate (Time) Interval*

At the 

RateInt

 prompt, press 

ENTER

  The monitor flashes the current time interval  If the current selection is correct, press 

ENTER

 to advance to the next parameter  To change to an alternate time interval, press 

UP

 or 

RIGHT

 to scroll to the correct 

time interval  Press 

ENTER

 to save and advance to the 

RateUnt

 parameter 

Select Flow Rate Units*

At the 

RateUnt

 prompt, press 

ENTER

  The monitor flashes the current rate unit  If the current selection is correct, press 

ENTER

 

to advance to the next parameter  To change to an alternate unit, press 

UP

 or 

RIGHT

 to scroll to the correct rate unit and press 

ENTER

 to save and advance to the 

TotlUnt

 parameter 

Select Units of Measure for Total*

At the 

TotlUnt

 prompt, press 

ENTER

  The monitor flashes the current total units  If the current selection is correct, press 

ENTER

 

to advance to the next parameter  To change to an alternate unit, press 

UP

 or 

RIGHT

 to scroll to the correct totalization unit  

Press 

ENTER

 to save and advance to the 

TotlMul

 parameter 

Select a Total Multiplier*

This parameter displays the accumulated flow total in multiples of 10  For example, if the optimum totalization unit is 1000 

gallons, the unit total display increments by one digit for every 1000 gallons monitored  In 

Run

 mode, at 1000 gallons the total 

monitor reads 1, at 3000 gallons, the total display reads 3  This feature eliminates having to look at a total, count the digits, 

and mentally insert commas for each 1000 multiple 
At the 

TotlMul

 prompt, press 

ENTER

   The monitor shows the current total multiplier  If the selection is correct, press 

ENTER

 to 

advance to the next parameter  To change to an alternate multiplier, press 

UP

 or 

RIGHT

 to scroll to the correct multiplier unit 

and press 

ENTER

 to and advance to the next parameter  

OTEE:

N

If the 

RateUnt

 or 

TotlUnt

 parameter has been set to pounds or kilograms, the monitor advances to the 

Spec Gr

 

parameter  At any other setting, the monitor advances to 

Scale F

  If pounds or kilograms have not been chosen, see 

Enter a Scale Factor on page 18

 

OTEE:

N

If you are in 

Programming

 mode, the monitor advances to the 

PulsOut

 parameter   

See 

Totalizer Pulse Output* on page 19

 

Enter a Specific Gravity Value* 

Mass readings in the ER-500 monitor are not temperature or pressure compensated so it is best to enter the specific gravity 

of the fluid as close to the system running temperature as possible  As liquids are essentially incompressible, pressure 

compensation is not necessary for liquids 
At the 

Spec Gr

 prompt, press 

ENTER

  The most significant digit of the current specific gravity flashes  If the current specific 

gravity is correct, press 

ENTER

 to advance to the next parameter  To change to an alternate specific gravity, press 

UP

 to 

increment the flashing digit until you reach the first digit of the new specific gravity  Press 

RIGHT

 to move to the next digit  

When all digits have been entered, press 

ENTER

 to save and advance to the 

Scale F

 parameter 

Programming

DSY-PM-00028-EN-02

Page 17 

February 2017

Содержание ER-500

Страница 1: ...Display ER 500 Advanced DSY PM 00028 EN 02 February 2017 Programming Manual...

Страница 2: ...ER 500 Flow Monitor Page ii February 2017 DSY PM 00028 EN 02...

Страница 3: ...9 Programming Using Frequency Output Flow Sensors 9 Menu Structure 10 Standard ER 500 Rate SU is Set to Simple 10 Advanced ER 500 Basic Menu 11 Standard ER 500 Rate SU is Set to Advanced 12 Advanced E...

Страница 4: ...ER 500 Flow Monitor Page iv February 2017 DSY PM 00028 EN 02...

Страница 5: ...avoided could result in severe personal injury or death Indicates a hazardous situation which if not avoided is estimated to be capable of causing minor or moderate personal injury or damage to proper...

Страница 6: ...a frequency output The output signal for these type of sensors is a frequency proportional to the rate of flow The ER 500 monitor uses the frequency information to calculate flow rate and total flow...

Страница 7: ...e that came with the IOG meter For instructions on programming the K factor see Enter Flow Sensor s K factor on page 17 Transmitter Connections The ILR transmitter typically used with the IOG meter fa...

Страница 8: ...he current loop is used a sensing circuit within the monitor detects the presence of the current loop and automatically disconnects the battery from the circuit JP1 JP2 JP3 Input Total Pulse Signal P1...

Страница 9: ...hen the grand total Modes RUN Normal operating mode PROGRAM Used to program parameters in the display EXTENDED PROGRAMMING Used to program advanced variables into the display TEST Used as a diagnostic...

Страница 10: ...ape Key Rate SU Rate Unit Setup Simple Advanced Flo Unt Rate Total Units GPM Gal OB D BBL m D m m H m LPM Ltr Gallons Min Gallons Oil Barrel Day Barrels Meters Day Meters Meters Hour Meters Liters Min...

Страница 11: ...rs T Meters T Feet T Million Gallons T Kilograms T Pounds T MASS TotalUnt Totalizer Unit Gal LBL OBL AFt MLt LPT m Ft MGa Kgs Lbs Gallons Liquor Barrel Oil Barrel Acre Feet Million Liters Liters Meter...

Страница 12: ...rel T Oil Barrel T Acre Feet T Million Liters T Liters T Meters T Feet T Million Gallons T Kilograms T Pounds T MASS TotalUnt Totalizer Unit Gal LBL OBL AFt MLt LPT m Ft MGa Kgs Lbs Gallons Liquor Bar...

Страница 13: ...Output Numeric Entry 4 20Tst 4 20 mA Output Numeric Entry Numeric Entry Numeric Entry Coef 1 Coefficient 1 Numeric Entry Freq x Frequency 2 10 Numeric Entry Coef x Coefficent 2 10 Numeric Entry NO YE...

Страница 14: ...t T Million Liters T Liters T Meters T Feet T Million Gallons T Kilograms T Pounds T MASS TotalUnt Totalizer Unit Gal LBL OBL AFt MLt LPT m Ft MGa Kgs Lbs Gallons Liquor Barrel Oil Barrel Acre Feet Mi...

Страница 15: ...e Output Disable Enable Numeric Entry Fl 20mA Flow at 20 mA Continued from previous page Modbus Address 1 to127 BusAddr Clr G T Clear Grand Total Passwd Password Modbus Disable Enable Numeric Entry Se...

Страница 16: ...in addition to the current total totalizer on the display and is always enabled In addition the grand total screen displays the number of times the grand total has reached its maximum count 9 999 999...

Страница 17: ...ompt press ENTER The monitor flashes the current total units If the current selection is correct press ENTER to advance to the next parameter To change to an alternate unit press UP or RIGHT to scroll...

Страница 18: ...Cutoff parameter NOTE N If the number you enter is out of range the display flashes Limit and refuses the entry Low Flow Cutoff The flow cutoff shows low flow rates that can be present when pumps are...

Страница 19: ...oint 2 Gnd Total Reset Total Pluse Signal Gnd Mag Pulse Iso OC Low High Input Total Pulse Signal TB1 Open Drain FET Total Pulse Output 2 2 10K Pull up Resistor VCC Internal 100 mA Maximum Figure 9 Ope...

Страница 20: ...tment To set the 4mA Out value connect an ammeter in series with the loop power supply as shown in Figure 11 The 4 mA DAC setting is typically 35 50 At the 4mA Out prompt press UP to increase or RIGHT...

Страница 21: ...ance to the Coef 1 parameter Coefficient The coefficient is the value applied to the nominal K factor to correct it to the exact K factor for that point The coefficient is calculated by dividing the a...

Страница 22: ...nt the display digit until it matches the first digit of the new bus address Press RIGHT to advance to the next digit Repeat for all digits of the address Press ENTER to save the new address and advan...

Страница 23: ...transistor reacts around a setpoint by taking recent history into account Hysteresis prevents an output from turning on and off rapidly when the programmed flow rate is at or very near the setpoint Fo...

Страница 24: ...um Flow Output ON O F F 8 g p m S e t p o i n t 1 0 g p m Hysteresis 2 gpm Output OFF Figure 15 Setpoint example At the TripSP1 prompt press ENTER The tripping condition setting is displayed If the cu...

Страница 25: ...ulses when the count total reached 1000 you would have accumulated 1 gallon of liquid Using the same reasoning each individual pulse represents an accumulation of 1 1000 of a gallon This relationship...

Страница 26: ...values are Velocity 4 3 ft sec Inside Diameter of Pipe 3 068 in Find the area of the pipe cross section 2 3 068 2 Area r2 Area x 2 35 7 39 in2 Find the volume in 1 ft of travel 88 71in2 7 3 in2 x 12...

Страница 27: ...which order the words are sent as long as the receiving device knows which way to expect it Since word order is a common problem between devices many Modbus master devices have a configuration setting...

Страница 28: ...the OFF state 3 8 Spares Alarm Setpoint 1 9 0 Setpoint OFF 1 Setpoint ON Alarm Setpoint 2 10 0 Setpoint OFF 1 Setpoint ON 11 16 Spares Opcode 01 Read Coil Status This opcode returns the state of the...

Страница 29: ...ess the tab on the battery connector to release it from the circuit board see Figure 18 Freq In 4 20mA Iso Total Pluse TR_B TR_A RS485 Gnd Setpoint 1 Setpoint 2 Gnd Total Reset OC Total Pluse Signal G...

Страница 30: ...sistor Adjustable flow rate with programmable dead band and phase Maximum Voltage 28V DC Maximum Current 100 mA Pull Up Resistor External required 2 2 K ohm minimum 10 K ohm maximum Modbus Advanced On...

Страница 31: ...voltage is checked across or in parallel with the 4 20 mA terminals and current is checked with the ammeter in series with the 4 20 mA output No Rate or Total Displayed Check connection from meter s t...

Страница 32: ...ENTRIE THROUGH SUITA STRAIGHT THRU 5 WHEN SELECTING CABLE FOR CONNECTION TO TURBINE METER USE CABLE WITH THE FOLLOWING HAZARDOUS LOCATION 10 FT TO MAX 100 FT HAZARDOUS LOCATION CLASSIFIED CLASS I DIV...

Страница 33: ...THROUGH SUITABLY SIZED UL CSA CERTIFIED LIQUID TIGHT STRAIGHT THRU FITTINGS NOTES ON FLOW SENSOR 1 INTERCONNECTING CABLE CAPACITANCE AND INDUCTANCE PLUS THE CAPACITANCE AND INDUCTANCE OF THE MAGNETIC...

Страница 34: ...Display ER 500 Advanced INTENTIONAL BLANK PAGE DSY PM 00028 EN 02 Page 34 February 2017...

Страница 35: ...Programming Manual INTENTIONAL BLANK PAGE DSY PM 00028 EN 02 Page 35 February 2017...

Страница 36: ...2 55 5662 0882 Europe Middle East and Africa Badger Meter Europa GmbH Nurtinger Str 76 72639 Neuffen Germany 49 7025 9208 0 Europe Middle East Branch Office Badger Meter Europe PO Box 341442 Dubai Sil...

Отзывы: