Setup > Input/Output >Current Output
The current output, reset input and frequency/pulse/status output can be set up through the
SETUP > INPUT/OUTPUT
menus
An asterisk (*) indicates the parameter default
Current Output Submenus Options/Descriptions
OUTPUT SOURCE
*FLOW RATE
VELOCITY
SIGNAL STRENGTH
TEST MODE
DISABLED
Select the reading to be assigned to the 4…20 mA output
RANGE
*4-20 mA
0-20 mA
MIN VALUE
Enter the value of the reading at 4 mA Can also be the setting for the 0 mA setpoint when 4-20 mA
RANGE
is
selected Units and decimal places based on parameter selected Negative numbers accepted
MAX VALUE
Enter the value of the reading at 20 mA Units and decimal places based on parameter selected Negative
numbers accepted
TEST CURRENT
Available only when
OUTPUT SOURCE
is in
TEST MODE
Default 12 00 mA To check the wiring to the control
system or gauge, you can override the current output with a fixed current Numeric entry mA 0…22 mA
TRIM 4 mA
Available only when
OUTPUT SOURCE
is in
TEST MODE
Set the test current to 4 mA Adjusts output until PLC/
DCS/BAS reads 4 mA
TRIM 20 mA
Available only when
OUTPUT SOURCE
is in
TEST MODE
Set the test current to 20 mA Adjusts output until
PLC/DCS/BAS reads 20 mA
Parameter Descriptions by Menu
Page 25
May 2021
TTM-UM-02537-EN-06