Digital air- conditioner controller KR- 454
E84
Outputs (total current) overloaded
Position
:
All loads connected to the air-conditioner controller (motor valves,
relays, Webasto, etc.)
Reason
:
Drawing of total current at the relay outputs more than 2A
Loads without auxiliary relays connected directly to the air-conditioner
controller
Measure
: Check all outputs connected by relays (measure drawing of current at
terminal 15 - X10, Pin 2)
E85
Front box stage 1 overcurrent
Position
:
Front box driver's cockpit
Reason
:
Motor stiff (ball bearing damage, foreign substances)
Measure
:
Check and clean fan
E86
Front box stage 2 overcurrent
Position
:
Front box driver's cockpit
Reason
:
Motor stiff (ball bearing damage, foreign substances)
Measure
:
Check and clean fan
Note:
All shields of the sensor cables and the cables for the potentiometer
check-back of the water valves as well as the control cable of the roof
duct fans may only be connected to the air-conditioner controller with
vehicle-ground. Ground connections within the vehicle (frame) may lead
to uncontrolled error messages or to error functions of the air-
conditioner controller!