Digital air- conditioner controller KR- 454
Measure:
Check plug connection, valve and cable
Replace motor valve if necessary (No.1808.001.11)
E39
Prop valve roof duct upper deck potentiometer defective
Position:
The water valve is located behind the first step in the staircase central
entrance
Reason
:
Plug connection not plugged correctly
Valve defective
Cable squeezed or broken
Opening angle of motor valve too small
Measure:
Check plug connection, valve and cable
Replace motor valve if necessary (No.1808.001.11)
E40
Prop valve front box upper deck potentiometer defective
Position
:
The water valve is located above the air-conditioner compressor in the
engine compartment on the right side
Reason
:
Plug connection not plugged correctly
Valve defective
Cable squeezed or broken
Opening angle of motor valve too small
Measure:
Check plug connection, valve and cable
Replace motor valve if necessary (No.1808.001.11)
E41
Prop valve convector upper deck potentiometer defective
Position
:
The water valve is located above the driving axle, it is accessible
through the attendance flap in the luggage boot
Reason
:
Plug connection not plugged correctly
Valve defective
Cable squeezed or broken
Opening angle of motor valve too small
Measure:
Check plug connection, valve and cable
Replace motor valve if necessary (No.1808.001.11)
E42
Prop valve front box upper deck potentiometer defective
Position
:
The water valve is located in the engine compartment on the upper
right side
Reason
:
Plug connection not plugged correctly
Valve defective
Cable squeezed or broken
Opening angle of motor valve too small
Measure:
Check plug connection, valve and cable