7-7
Operation & Maintenance Manual
Doc. Ref. MNGRM2CO2 REV. 3
REPLACING THE NETWORK MODULE (INC. INSERT PLATE)
IMPORTANT:
Before powering off the system to change the network module:
1.
Using the latest version of the GRM2 configuration tool, ‘Load’ the configuration from the
GRM2. In order to do this you will need a working network connection to the GRM2 (refer to
section 4) and you will need to know the IP address of the GRM2 (refer to section 5-8)
You can now follow the below procedure for removal and refitting. When the network module
replacement is finished, and the system is powered back on:
2.
Using the latest version of the GRM2 configurati
on tool, ‘Load’ the configuration obtained in
step 1 above from your local file system and send this to the GRM2. You will need a working
network connection to the GRM2. The IP address of the GRM2 should be unchanged from
that used in step 1 above.
Procedure for removal and refitting:
Switch off the mains supply to the monitor
and wait for a few seconds while the power
supply discharges. Open the enclosure door
with the key provided and switch off at the
internal power input module using the red
button
(1)
.
Noting the sequence - Disconnect the power
supply cables
(2)
, cables to the enclosure
door
(3)
, the Styx module cables
(4)
, including
the ribbon cable
(7),
SAMM connections
(5)
,
ADC terminal panel cables
(6)
and any
remaining wired in connections.
Unscrew the six nuts holding the network
module in position
(8)
, located around the
edge of the insert plate, and remove the
module complete with insert plate.
Fit the new network module complete with
insert plate. Fit the shake-proof washers and
securing nuts and tighten. Reconnect all
cables previously disconnected. Check all
connections are secure. Switch the internal
power input module on by pressing the green
button. Close and lock the enclosure door
and reinstate the mains supply.
8
8
8
4
4
8
8
8
2
2
5
5
1
6
7
3
Содержание Parasense GRM2 CO2 Series
Страница 7: ...1 2 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 GENERAL ARRANGEMENT...
Страница 14: ...2 7 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 NETWORK MODULE CONNECTIONS...
Страница 73: ...1 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 9 APPENDIX GRM2 CO2 GENERAL ARRANGEMENT PM2067...
Страница 74: ......
Страница 75: ......
Страница 76: ...2 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 GRM2 CO2 CONNECTION SCHEMATICS PS0748...
Страница 77: ......
Страница 78: ......
Страница 79: ......
Страница 80: ......
Страница 81: ......
Страница 82: ...3 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 ADC 104 GENERAL ARRANGEMENT PM2098...
Страница 83: ......
Страница 84: ...4 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 ADC 104 PANEL MOUNTING DETAILS PM2247...
Страница 85: ......
Страница 86: ...5 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 ADC 104 CONNECTION SCHEMATIC PS0753...
Страница 87: ......
Страница 88: ......
Страница 89: ......
Страница 90: ...6 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 GRM2 CO2 WITH ADC 104 INSTALLATION OVERVIEW PS0790...
Страница 91: ......
Страница 92: ...7 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 RM2C 104 ATM2R CONNECTION DETAILS PS0768...
Страница 93: ......
Страница 94: ...8 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 NETWORK SENSOR MOUNTING AND CONNECTIONS PS0778...
Страница 95: ......
Страница 96: ......