Multi-Zone Gas Monitors
36
P/N: 3015-5074 Rev 11
4.4.6. Clearing the Alarm Event Log
A data log of the last 20 alarm events is retained in memory.
•
From the
Data Display Screen
, press the UP or DOWN arrow key. SETUP will be highlighted in
the first box.
•
Press the DOWN arrow key until
Alarm Event Log
is highlighted, then press
ENTER
to select this
option and display the
Alarm Event Log
(see below).
Figure 4-6. Acce ssing the Alarm Event Log
This screen lists zones in the left column and displays which alarms were associated with each zone as
represented by the vertical cursor bar. As you move the bar horizontally using the LEFT/RIGHT cursor keys,
the date and time the alarm condition was detected is displayed in the upper right hand corner of the display
window.
NOTE:
The Alarm E vent Log can be reset by pressing a combination of the ENTE R and
RIGHT arrow buttons while viewing the log.
4.5. System Faults
4.5.1. Functional Overview
If a system malfunction occurs, the yellow FAULT LED will glow. Additionally, an external alarm device may
activate and an audible alarm may sound if those features have been enabled (see
Connecting External
Alarms
on page 23 and
Audible Alarm
on page 26).
The next time the Remote Display polls the affected monitor its yellow FAULT LED will also glow.
Additionally, an external alarm device may activate and an audible alarm may sound if those features have
been enabled (see
Connecting External Alarms
on page 23 and
Audible Alarm
on page 26).
Depending on the nature of the fault, the MZ monitor may or may not continue to operate normally. Under a
non-critical fault condition, the MZ will continue to measure and log data, but some peripheral functions may
be compromised. Under a critical fault condition, action is required for the MZ monitor to operate normally.
The table on the following page lists the various fault conditions and explains what action should be taken to
correct the problem. Note that the fault codes are cumulative. For example, a code <4200> is both a
<4000> “RE ZERO VOLT TOL” and <0200> “GAIN SET FAULT” combined, indicating two simultaneous
faults.
Содержание MultiZone
Страница 52: ...Multi Zone Gas Monitors 46 P N 3015 5074 Rev 11 ...
Страница 58: ...Multi Zone Gas Monitors 52 P N 3015 5074 Rev 11 ...
Страница 60: ...Multi Zone Gas Monitors 54 P N 3015 5074 Rev 11 ...
Страница 71: ...Multi Zone Gas Monitors P N 3015 5074 Rev 11 65 APPENDIX C SYSTEM MENU MAP ...
Страница 72: ...Multi Zone Gas Monitors 66 P N 3015 5074 Rev 11 ...
Страница 73: ...Multi Zone Gas Monitors P N 3015 5074 Rev 11 67 APPENDIX D AGENCY APPROVALS ...
Страница 74: ...Multi Zone Gas Monitors 68 P N 3015 5074 Rev 11 ...
Страница 76: ...Multi Zone Gas Monitors 70 P N 3015 5074 Rev 11 ...
Страница 78: ...Multi Zone Gas Monitors 72 P N 3015 5074 Rev 11 ...