background image

Instruction 0019-9210 

13

The Informant Refrigerant Leak Detector

Operation

Sensor Flooding Indication

When the sensor becomes 

fl

 ooded with a high concentration of refrigerant, 

observe that the gas-level LED’s quickly light full scale and then all turn 

off, leaving both the audible tick rate and probe tip blink rate at elevated 

levels. When this condition occurs, move the detector to an area of fresh 

air until all indicators return to their idle state.

SAE Leak Detection Tips

The following was derived from SAE Surface Vehicle Standard J1628, 

Technician Procedure for Using Electronic Refrigerant Leak Detectors for 

Service of Mobile Air-Conditioning Systems:

• The electronic leak detector shall be operated in accordance with the 

equipment manufacturer’s operating instructions.

• Leak test with the engine not in operation.

• The air conditioning system shall be charged with suf

fi

 cient refrigerant 

to have a gauge pressure of at least 340 kPa (49 psi) when not in opera-

tion. At temperatures below 15 °C (59 °F), leaks may not be measurable, 

since this pressure may not be reached.

• Take care not to contaminate the detector probe tip if the part being 

tested is contaminated. If the part is particularly dirty, it should be 

wiped off with a dry shop towel or blown off with shop air. No cleaners 

or solvents shall be used, since many electronic detectors are sensitive to 

their ingredients.

• Visually trace the entire refrigerant system, and look for signs of air-

conditioning lubricant leakage, damage, and corrosion on all lines, hos-

es, and components. Each questionable area shall be carefully checked 

with the detector probe, as well as all 

fi

 ttings, hose-to-line couplings, 

refrigerant controls, service ports with caps in place, brazed or welded 

areas, and areas around attachment points and hold-downs on lines and 

components.

• Always follow the refrigerant system around in a continuous path so 

that no areas of potential leaks are missed. If a leak is found, always 

continue to test the remainder of the system.

Содержание Informant Leak Detector

Страница 1: ...0019 9210 1 The Informant Refrigerant Leak Detector The Informant Refrigerant Leak Detector Instruction 0019 9210 Operation Maintenance Rev 6 May 2010 Quality Products Nationwide Repair Service Techni...

Страница 2: ...d to those provided herein to the exclusion of any and all other remedies including without limitation incidental or consequential damages No agreement varying or extending the foregoing warranties re...

Страница 3: ...ocedure for Locating a Refrigerant Leak 7 Sensor Failure Indication 8 False Refrigerant Indication 8 Sensor Flooding Indication 9 SAE Leak Detection Tips 9 Maintenance 11 Routine Maintenance 11 Probe...

Страница 4: ...The Informant Refrigerant Leak Detector 4 Instruction 0019 9210 Notes...

Страница 5: ...s or refrigerant are present No man ual sensitivity adjustments are necessary during the inspection process The detector is suitable for HVAC Service Technicians Refrigerant Ser vice Technicians Plant...

Страница 6: ...itivity mode pushbutton selectable Automatic zero and background compensation that allows a leak to be quickly found in contaminated atmospheres without requiring manual sensitivity adjustments Flexib...

Страница 7: ...LED Probe tip is 0 2 5 mm in diameter and 1 25 mm long Battery Life 4 5 hours under typical intermittent opera tion Visual and Audible Indicators Power On Green LED Low Battery Red LED Low Sensitivity...

Страница 8: ...efrigerant as detected by mov ing probe tip at 2 50 mm per second 0 1 3 mm above leak source A leak rate of less than 0 25 oz year 7 g yr can be de tected when probe tip is held steady over leak sourc...

Страница 9: ...ee Figure 3 The detector is toggled ON and OFF by pressing the POWER button When first turned on observe that the Power LED glows and that all other LED s are tested by being turned on for 1 second Th...

Страница 10: ...oggled on and off by momen tarily pressing the LOW SENS MUTE button for less than second ob serve that the LOW SENS LED should not be affected by this operation Normal Low Sensitivity Mode When The In...

Страница 11: ...allows an operator to quickly locate the source of a leak without making manual sensitivity adjust ments or being concerned about the background vapor or refrigerant level in the surrounding area Lea...

Страница 12: ...refrigerant level indicators will all begin to decrease At this point reverse the direction of probing As the probe tip is moved back and forth across the leak the detector will automatically adjust...

Страница 13: ...to have a gauge pressure of at least 340 kPa 49 psi when not in opera tion At temperatures below 15 C 59 F leaks may not be measurable since this pressure may not be reached Take care not to contamina...

Страница 14: ...Leak testing of the evaporator core while in the air conditioning module shall be accomplished by turning the air conditioning blower on high for a period of 15 seconds minimum shutting it off then wa...

Страница 15: ...rant This will severely reduce sensor life or damage the sen sor Routinely check the probe filter A dirty filter will lengthen the detec tor s response time or prevent the detection of gas if the filt...

Страница 16: ...quired Probe Filter refer to Section Replacement Parts Procedure 1 Turn OFF detector 2 Unscrew probe tip 3 Remove filter from top of sensor and discard 4 Insert replacement filter 5 Reinstall probe ti...

Страница 17: ...SING Procedure 1 Turn OFF detector 2 Unscrew probe tip 3 Remove filter from top of sensor then pull out sensor from its socket and discard 4 Plug in new sensor making sure that its tab lines up with n...

Страница 18: ...ors from the printed circuit board being very careful not to damage the pins on the board then remove the probe assembly from the detector 5 Remove fan from probe assembly by removing its three screws...

Страница 19: ...See Figure 6 for instructions on how to remove Front Retaining Collar 8 Position the probe assembly between the two case halves routing the fan wires through the notches in the case as shown in Figur...

Страница 20: ...TTOM OF CASE Pry off front retaining collar by inserting a flat blade screwdriver here and twisting When replacing collar ensure that rib inside collar shown here in dotted lines fits into slot in bot...

Страница 21: ...gerant Leak Detector PROBE FAN BATTERY IMPORTANT IMPORTANT When installing connectors be sure to position their wires as illustrated Route wires from fan through notches in case Figure 8 Connector Loc...

Страница 22: ...d con nector Disassemble detector and ensure that all connectors are securely attached to the printed circuit board See Figure 8 Sensor depleted or faulty Replace sensor per Section Sensor Replace men...

Страница 23: ...mly in socket b Sensor has often been exposed to high levels of refrigerant Avoid sampling to pure refrigerant for long periods of time a Probe filter clogged Replace filter per Section Probe Filter R...

Страница 24: ...t includes protective rubber boot MagLite 2 AA batteries and a hard carrying case 0019 8037 Protective Rubber Boot provides a protective cover for the Informant that includes a cavity for a MagLite fl...

Страница 25: ...y contacting one of the following Bacharach Sales Service Centers United States Bacharach Inc 621 Hunt Valley Circle New Kensington PA 15068 Phone 724 334 5051 Fax 724 334 5723 Email help bacharach in...

Страница 26: ...The Informant Refrigerant Leak Detector 26 Instruction 0019 9210 Notes...

Страница 27: ...Instruction 0019 9210 27 The Informant Refrigerant Leak Detector...

Страница 28: ...eak Detector 28 Instruction 0019 9210 Headquarters 621 Hunt Valley Circle New Kensington PA 15068 Ph 724 334 5000 Fax 724 334 5001 Toll Free 800 736 4666 Website www mybacharach com E mail help mybach...

Отзывы: