MGS-250 Manual
6490-9000 Revision 4
25
3.3. Wiring Alarm Output (Analog Signal)
The MGS-250 provides an analog output signal that is proportional to the
level of gas detected.
NOTE:
No jumpers or hardware switch settings are required
to configure the analog output. This is done electronically
from the front panel display.
Connect two 18 to 20 AWG wires to terminal block positions 5 and 6 (see
Figure 10), noting ground and signal polarity per Table 6.
Figure 10. Analog Output Wiring
Table 6: Alarm Output Terminal Block Connections
Function
Pin
Wiring Termination
Analog
Output
5
Analog output ground
6
Analog output signal (+)
The type of output signal on pins 5 and 6 is programmable using the
analog output type parameter P.-03. Refer to Section 5 for details.