MGS-250 Manual
6490-9000 Revision 4
23
3.2. Wiring Supply Power (24VAC or 24VDC)
WARNING:
Incorrect wiring may permanently damage the gas
detector, and void the warranty. Double check all terminations
before applying power.
Either 24VAC or 24VDC may be used to power the MGS-250. Connect
wiring to the appropriate terminal locations (see Table 5). Use 2 wires,
between 14 and 22 AWG. Refer to Figure 8 for (AC wiring left) or DC
wiring (right).
Figure 8. Supply Power Wiring Options
Table 5: Power Options and Terminal Block Connections
Power Option
Pin
Label
Wiring Termination
24 VAC
1
L
24V AC line
2
N
24V AC neutral
24 VDC
3 +
24V
DC
positive
4 GND
24V
DC
ground
www.calcert.com
1.888.610.7664
0
5
10
15
20
25
30