![BAC TrilliumSeries DFCV Series Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/bac/trilliumseries-dfcv-series/trilliumseries-dfcv-series_rigging-and-installation-instructions_3379915021.webp)
5 Inspection Prior to Start-up
5 Inspection Prior to Start-up
W W W . B A L T I M O R E A I R C O I L . E U
21
INSPECTION PRIOR TO START-UP
Start-up and Commissioning
ROTATION OF FANS
Fans must rotate without obstruction in the direction indicated by arrows on the equipment.
MOTOR VOLTAGE AND CURRENT
Check the voltage and the current of all three legs of the fan motors. The current should not exceed the nameplate
rating. After prolonged shutdown the motor insulation should be checked with a Megger insulation tester prior to
restarting.
The voltage must not fluctuate more than +/-10% and the imbalance between phases must not be greater
than +/-2%.
UNUSUAL NOISE AND VIBRATIONS
Unusual noise and/or vibration are the result of malfunctioning of mechanical components or operational problems
(e.g. unwanted ice formation). If this occurs, a thorough inspection of the entire unit followed by immediate
corrective action is needed. If required, consult your local BAC Balticare representative for assistance.
PURGE REQUIREMENTS
The installer of BAC closed circuit cooling towers must ensure a proper air purging of the system prior to operation.
Entrained air can restrict the capacity of the cooler, resulting in higher process temperatures.
All connections (installed by others) must be leak free and tested accordingly.
TrilliumSeries Coolers with factory installed control
panel with Variable Frequency Drive
ELECTRICAL PANEL
All units are equipped with an electrical panel with Variable Frequency Drive.
When operating above nominal speed, be aware of the potential risk for overload or mechanical damages.
DFCV
DFCV-AD
5
Содержание TrilliumSeries DFCV Series
Страница 1: ...DFCV Dry Cooler DFCV AD Adiabatic Cooler RIGGING AND INSTALLATION INSTRUCTIONS RDFCV ADv15EN...
Страница 10: ...8 fan unit 10 fan unit 12 fan unit W W W B A L T I M O R E A I R C O I L E U 10...
Страница 19: ...Installing screw on flange W W W B A L T I M O R E A I R C O I L E U 19 3 Section Assembly 3 Section Assembly...
Страница 26: ...W W W B A L T I M O R E A I R C O I L E U 26...
Страница 27: ...W W W B A L T I M O R E A I R C O I L E U...
Страница 28: ...W W W B A L T I M O R E A I R C O I L E U...
Страница 29: ...W W W B A L T I M O R E A I R C O I L E U...
Страница 30: ...W W W B A L T I M O R E A I R C O I L E U...
Страница 31: ...W W W B A L T I M O R E A I R C O I L E U...