Typically disinfection is achieved using a sodium hyper chloride solution to maintain a residual value of 5 - 15 mg/l
of free chlorine and circulate this around the system for up to 6 hours. Higher chlorine levels for a shorter period are
possible, but require a higher level of corrosion protection than galvanized steel only. Consult your BAC Balticare
representative for further information.
Excessive levels of chlorine must be avoided as this quickly can lead to corrosion and damage to your system.
Chlorinated water should be de-chlorinated before draining and after disinfection the system must be thoroughly
flushed through with clean water.
A proper regularly monitored biocide programme reduces the need for cleaning and disinfection actions
significantly.
W W W . B A L T I M O R E A I R C O I L . E U
37
5 Maintenance Procedures
5 Maintenance Procedures