background image

www.babbittinternational.com 

Reference Manual 

 

2021

 

 

 

14 

 

 

Содержание LS8500

Страница 1: ...LS8500 Presence Absence Switch OWNERS MANUAL INSTALLATION CALIBRATION TROUBLESHOOTING WARRANTY P O Box 70094 Houston TX 77270 713 467 4438 ...

Страница 2: ...s arise during installation please contact Customer Service 1 800 835 8012 or 713 467 4438 8 00 a m to 5 00 p m CST US Failure to follow safe installation and servicing guidelines could result in death or serious injury Make sure only qualified personnel perform the installation Use the equipment only as specified in this manual Failure to do so may impair the protection provided by the equipment ...

Страница 3: ...tial Ring Flange Location 8 3 3 2 Full Ring Flange Location 8 3 3 3 Full Faced Gaskets Flanges 8 3 4 Physical Installation 10 3 4 Grounding 10 3 5 Ground Continuity Test 10 3 6 Installing the Receiver 11 3 7 Typical Applications Wiring Diagrams 12 4 CALIBRATION 16 4 1 Sensitivity Calibration Conductive Materials 16 4 2 Sensitivity Calibration Non Conductive Materials 17 4 3 Time Delay 18 4 3 Setti...

Страница 4: ...e receiver changes state when material is detected 1 2 Specifications Electrical Power 115 VAC 15 50 60 Hz 2 watts standard 12 VDC 24 VDC or 230 VAC optional Output 2 Form C contacts DPDT relay 5 amp resistive at 125 250 VAC 30 VDC Fuse On board 250 mA 125 volts Fail Safe Selectable high or low level Time Delay Selectable ON or OFF delay Adjustable 1 8 sec to 2 hours RF Frequency Approximately 1 3...

Страница 5: ...ional com Reference Manual 2021 5 1 3 Ordering Information LS8500 115VAC FP 4 150 PR Model LS8500 Power Supply 115VAC 24VDC 12VDC 220VAC Sensor Type FP Flange Probe Sensor Size Flange Model PR Partial Ring or FR Full Ring ...

Страница 6: ...www babbittinternational com Reference Manual 2021 6 1 4 GA Drawing Figure 1 1 1 5 Sensor Rings Figure 1 2 ...

Страница 7: ...hed 2 A transmitter module in the explosion proof enclosure 3 The LS8000 R receiver card 4 A plastic snap track to mount the receiver card 3 2 Bench Test THIS IS AN EXCELLENT TIME TO TEST AND BECOME FAMILIAR WITH THE TIME DELAY IF IT IS TO BE USED IN YOUR APPLICATION See calibration instructions section 7 1 and 7 2 On the bench hook up the appropriate power to L1 and L2 The operating voltage of th...

Страница 8: ...f problematic locations and preferred locations Areas to avoid include immediately before or after a 90 degree bend vertical or horizontal pipe In some cases these areas have created air pockets thus turning the pump off In other cases these areas have led to excess buildup leaving pumps to run when they should have been turned off 3 3 2 Full Ring Flange Location Full ring sensor flanges are prima...

Страница 9: ...www babbittinternational com Reference Manual 2021 9 SENSOR FLANGE MOUNTING ...

Страница 10: ...and water will stay outside the unit install an EYSM unilet before each LS8500 and fill with explosion proof sealing cement CAUTION Always take the necessary safety precautions when cutting or welding a Tag and lock out the electrical power to the equipment that services the vessels b Check liquid or dry powders that create a gas in the vessel for oxygen as well as the explosion factor All dust wi...

Страница 11: ... be mounted in existing control panels or enclosures can be ordered from the factory 1 Attach the snap track to the panel back pan or other surface using 2 small screws or a suitable adhesive 2 Snap the LS8000 R same as LS8500 receiver card into the snap track 3 Connect shielded cable to the 3 terminals marked G S see page 13 for wiring diagram 4 Connect the proper supply voltage and relay output ...

Страница 12: ...R RECEIVER IS INTENDED FOR ONLY SUPPLY VOLTAGE THIS VOLTAGE IS PRINTED ON THE POWER SUPPLY BOARD FOR 115VAC OR 230VAC UNITS HOOK UP THE HOT LEAD TO L1 AND THE NEUTRAL TO L2 WITH APPROPRIATE GROUND FOR 12 VDC OR 24 VDC UNITS HOOK THE POSITIVE VOLTAGE TO L1 AND THE COMMON OR GROUND TO L2 NOTE LS8000 AND LS8500 ELECTRONIC COMPONENTS ARE INTERCHANGABLE ...

Страница 13: ...www babbittinternational com Reference Manual 2021 13 ...

Страница 14: ...www babbittinternational com Reference Manual 2021 14 ...

Страница 15: ...www babbittinternational com Reference Manual 2021 15 ...

Страница 16: ...w babbittinternational com Reference Manual 2021 16 4 CALIBRATION 4 1 Sensitivity Calibration Conductive Materials NOTE The green LED indicates relay status The relay is energized when the green LED is on ...

Страница 17: ...www babbittinternational com Reference Manual 2021 17 4 2 Sensitivity Calibration Non Conductive Materials NOTE The green LED indicates relay status The relay is energized when the green LED is on ...

Страница 18: ... timing ranges you can set the timer for a shorter range then change the range switches S1 and S2 to increase the time For example the desired time delay is 15 minutes This is equal to 900 seconds By setting S1 down and S2 up and adjusting the timer to approximately 28 seconds the ratio on this range is 1 To increase this range by 32 move S1 up and S2 up 32x28 seconds equals approximately 15 minut...

Страница 19: ...t so that the bare end is not touching anything Turn calibration Pot 20 turns CCW LED should go out If it does repair replace or clean flange If LED does not go out replace electronics Check shielded cable for proper connection Check shielded cable for shorts or open circuits Unit triggers when material Improper mounting of flange Contact factory or distributor touches sensing element Improper cal...

Страница 20: ...r workmanship All claims must be made in writing within the warranty period No claims outside of the warranty period will be honored Warranties are not applied to any components which have been damaged by improper installation use exposure to unusual atmospheric conditions or components which have been misused abused damaged by neglect or accident This warranty shall not apply to any components wh...

Отзывы: