BABBITT LS7000 Скачать руководство пользователя страница 7

www.babbittinternational.com

 

Reference Manual 

 

2021

 

 

 

4) 

CAUTION: 

Always take the necessary safety precautions when cutting or welding in the coupling for 

 

 

         the LS7000. 
         a) Tag and lock out the electrical power to the equipment that services the vessels. 
         b) Check liquid or dry powders that create a gas in the vessel for oxygen as well as the 

 

 

     explosion factor. (All dust will explode.) 

         c) Vessels that are cross vented have to be isolated. 
 

       5)   Screw the LS7000 into the connection provided. In dry material applications, no sealant on the threads           
 

is required. On liquid applications, Teflon or a good pipe thread sealant may be used. 

       6)   The LS7000 has a 1” conduit entry. When wiring these units, conform to the National Electrical Code 
  

and any other city or company codes.  

       7)   Always install the electrical connection into the 1” conduit entry on the LS7000 so water will not 
 

follow the connection routing into the threads of the conduit hub. To guarantee that condensation and 

 

water will stay outside the unit, install an EYSM unilet before each LS7000 and fill with explosion 

 

proof sealing cement. 

        8) When required, the LS7000 probe can be bent to meet your special application. Remember to allow 2” 
 

of clearance between the probe and the vessel wall. If the probe is to be used in a pressure application, 

 

the factory must bend the probe to your specifications.  

 
         9) Location of probes on high level installations is more critical on dry materials than liquids. Note the 
 

following: 

 

 

a) For dry materials, mount the LS7000 in the top of the vessel whenever possible. (This allows you to 

 

 

     lengthen the probe if necessary.) 

 

 

b) Avoid mounting the LS7000 near the product inlet, vent return lines, dust collectors and vessel  

 

      

    discharge openings on dry materials. Turbulence around these areas can cause erratic detection  

 

      

    unless the probe is long enough. On old installations it might be wise to fill the vessel first to  

 

 

    determine the length of the probe. We recommend a 36” top mounted high level probe in storage 

 

 

     silos and 24” in smaller vessels such as bins. 

 
 
 

 

c) On gravity filled vessels, take into consideration the angle of repose formed by the product. 

 

 

d) On dry product that flows like water (starch), when using the LS7000 to stop the flow by means of 

 

 

     a butterfly valve or knifegate, make sure the probe is long enough to allow time to close these slow 

 

 

     moving valves. 

  

 

e) In small vessels where a good location is hard to find, it may be necessary to put a baffle plate  

 

 

    between the probe and the product inlet to keep product off of the probe as it fills. (A short time              

 

 

    delay could also solve this problem.) 

 

3.4 Removing the Electronics 

 

1)   To remove the sensing card, simply unplug it from the power supply card. When reinstalling, this card 

 

 

is made so that it cannot be plugged in backwards. 

       2)   To remove the power supply card you must: 

 

a) Disconnect supply power at main power source. 

 

b) Remove sensing card. 

 

c) Disconnect wires from terminal strip. 

 

d) Remove green grounding screw. 

 

e) Unplug blue antenna lead. 

 

f) Hold the top of the card guide and lift out 

 

    To reinstall, reverse the above procedure. 

 CAUTION:

 Always take safety precautions before opening vessels for such inspections. 

 

Содержание LS7000

Страница 1: ...LS7000 LEVEL SWITCH OWNERS MANUAL INSTALLATION CALIBRATION TROUBLESHOOTING WARRANTY P O Box 70094 Houston TX 77270 713 467 4438...

Страница 2: ...r problems arise during installation please contact Customer Service 1 800 835 8012 or 713 467 4438 8 00 a m to 5 00 p m CST US Failure to follow safe installation and servicing guidelines could resul...

Страница 3: ...tion 5 1 4 GA Drawing 5 3 INSTALLATION 6 3 1 Inspection 6 3 2 Bench Test 6 3 3 Physical Installation 6 3 4 Removing the Electronics 7 3 5 Typical Applications and Wiring Diagrams 8 4 CALIBRATION 14 4...

Страница 4: ...rical Power 115 VAC 15 50 60 Hz 2 watts standard 12 VDC 24 VDC or 230 VAC optional Output 2 Form C contacts DPDT relay 5 amp resistive At 125 250 VAC 30 VDC Fuse On board 250 mA 125 volts Fail Safe Se...

Страница 5: ...www babbittinternational com Reference Manual 2021 5 1 3 Ordering Information 1 4 GA Drawing...

Страница 6: ...2 On the bench hook up the appropriate power to L1 and L2 The operating voltage of the LS7000 is marked on the power supply board Hold the unit so that nothing is touching any surface and press the t...

Страница 7: ...dry materials mount the LS7000 in the top of the vessel whenever possible This allows you to lengthen the probe if necessary b Avoid mounting the LS7000 near the product inlet vent return lines dust c...

Страница 8: ...ONTACTS SUPPLY VOLTAGE NOTE EACH LS7000 POWER SUPPLY IS INTENDED FOR ONLY ONE SUPPLY VOLTAGE THIS VOLTAGE IS PRINTED ON THE POWER SUPPLY BOARD FOR 115 VAC OR 230 VAC UNITS HOOK UP THE HOT LEAD TO L1 A...

Страница 9: ...www babbittinternational com Reference Manual 2021 9...

Страница 10: ...www babbittinternational com Reference Manual 2021 10...

Страница 11: ...www babbittinternational com Reference Manual 2021 11...

Страница 12: ...www babbittinternational com Reference Manual 2021 12...

Страница 13: ...www babbittinternational com Reference Manual 2021 13...

Страница 14: ...E S3 and S4 also select fail safe high level FSH or fail safe low level FSL 2 Select the timing range using S1 and S2 as shown on the chart below next page 3 Adjust the time adjustment potentiometer c...

Страница 15: ...djustment potentiometer clockwise CW until it comes on 3 Turn the sensitivity adjustment pot counter clockwise CCW until the Red LED just goes out This sets the unit to its maximum sensitivity If in y...

Страница 16: ...go out If it does repair replace or clean antenna probe If LED does not go out replace electronics Bad sensing card Repair or replace card Unit triggers when material Improper mount of probe Contact...

Страница 17: ...applied to any components which have been damaged by improper installation use exposure to unusual atmospheric conditions or components which have been misused abused damaged by neglect or accident Th...