7.  Attach tether wire under screw head at the base 

of the UPM housing and tighten. Slowly lower 

the faceplate until tether is taut. 

 NOTE: Faceplate tether supplied with UPM 

is designed as an installation aid and NOT a 

safety cable. Do not add weight to, or drop 

faceplate.

RELEASE DATE

2-26-19

REFERENCE

 

NUMBER

INS-2794-02

40429 Brickyard Drive • Madera, CA 93636 • USA

559.438.5800 • FAX 559.438.5900 

www.bklighting.com • [email protected]

B-K LIGHTING

Ground

Hot

Neutral

A

B

C

Ground

Hot

Neutral

A

B

C

6.  If UPM housing is not level, remove UPM housing; 

loosen but 

DO NOT REMOVE

 (2) #8-32 screws 

with 9/64” Allen wrench on CamLock™ assembly. 

Adjust CamLock™ assembly up to 30° as needed 

to level. Tighten the screws and reattach UPM 

housing. 

10.  Make sure UPM housing gasket is free of any dirt 

or debris. Attach the faceplate by tightening the 

(4) #6-32 captive screws evenly using a 5/64” 

Allen wrench.

Ground

Hot

Neutral

A

B

C

Ground

Hot

Neutral

A

B

C

Ground

Hot

Neutral

A

B

C

1.  Install standard 4.5” x 2.85” recessed junction box 

(By Others) in the final fixture location according 

to designed lighting plan.

 NOTE: Vertical or horizontal installation of 

recessed junction box determines orientation 

of UPM.

2.  Pull branch circuit wiring necessary for installation 

(By Others.)

3.  Feed branch circuit wiring and lamp leads to 

remote mounted fixture through mounting plate 

with CamLock™ assembly. Attach mounting plate 

with supplied (2) #6-32 stainless steel hex drive 

fasteners to recessed junction box using a 5/64” 

Allen wrench.

4.  Feed wire into UPM housing. Install housing 

on CamLock™ at 90° to finished orientation as 

shown. (Figure A)

5.  Rotate housing 90° counter-clockwise (Figure 

B). Tighten set screw with 5/64” Allen wrench 

on outside of UPM housing to lock in place.  

(Figure C)

IMPORTANT SAFETY INFORMATION LISTED ON REVERSE

READ, FOLLOW, AND SAVE ALL SAFETY AND INSTALLATION INSTRUCTIONS

Installation Instructions

PM2RM RECTANGULAR CAMLOCK™

10W Driver Housing

LINE

Red

FIXTURE

COM

Hydrolock

Plate

Black

GROUND

Driver

White
Black
Green

DIM +
DIM -

Black
White

Hydrolock

Plate

Green

Driver

White
Black
White
Blue
Green

LINE

COM

GROUND

Orange
Orange
Brown
Blue

Black
Gray

FIXTURE

FIXTURE

Green

Green

LINE

Red

FIXTURE

COM

Driver

Black

GROUND

DIM +
DIM -

GROUND IN HOUSING

LINE

Red

FIXTURE

COM

Driver

Black

DIM +
DIM -

GROUND ON PLATE

LINE

Red

FIXTURE

COM

Driver

Black

DIM +
DIM -

HP2RM

HP2 TR

TMB

PCIII

Generic TR

GROUND IN HOUSING

LINE

Quick

Connect

COM

Driver

FIXTURE

DIM +
DIM -

PM3

GROUND IN HOUSING

LINE

Quick

Connect

COM

Driver

FIXTURE

DIM +
DIM -

Quick

Connect

Driver

FIXTURE

DIM +
DIM -

PM3D

GROUND IN HOUSING

LINE

COM

Remote

Driver

DIM +
DIM -

Fixture
Fixture

GROUND ON PLATE

LINE

COM

Driver

DIM +
DIM -

PCIII

Quick

Connect

FIXTURE

LINE

Red

FIXTURE

COM

Remote

Driver

Black

DIM +
DIM -

MA/AP

GROUND

GROUND IN HOUSING

LINE

COM

Remote

Driver

DIM +
DIM -

DIM +
DIM -

Fixture

Fixture

Remote

Driver

Fixture

Fixture

LINE

COM

Remote

Driver

GROUND

F
Fixture -

GROUND IN HOUSING

LINE

COM

Remote

Driver

F
Fixture -

Remote

Driver

F
Fixture -

GROUND IN HOUSING

LINE

COM

Remote

Driver

F
Fixture -

WIRING DIAGRAM - 010 Control Type

9.  Use waterproof wire connectors (By Others) to 

connect driver primary leads to branch circuit 

wires. Connect incoming ground to ground wire 

provided in UPM housing. Connect incoming 

dimming control wires to driver dimming 

controls. Connect secondary leads to fixture 

leads. 

See wiring diagram.

LINE

Red

FIXTURE

COM

Hydrolock

Plate

Black

GROUND

Driver

White
Black
Green

DIM +
DIM -

Black
White

Hydrolock

Plate

Green

Driver

White
Black
White
Blue
Green

LINE

COM

GROUND

Orange
Orange
Brown
Blue

Black
Gray

FIXTURE

FIXTURE

Green

Green

LINE

Red

FIXTURE

COM

Driver

Black

GROUND

DIM +
DIM -

GROUND IN HOUSING

LINE

Red

FIXTURE

COM

Driver

Black

DIM +
DIM -

GROUND ON PLATE

LINE

Red

FIXTURE

COM

Driver

Black

DIM +
DIM -

HP2RM

HP2 TR

TMB

PCIII

Generic TR

GROUND IN HOUSING

LINE

Quick

Connect

COM

Driver

FIXTURE

DIM +
DIM -

PM3

GROUND IN HOUSING

LINE

Quick

Connect

COM

Driver

FIXTURE

DIM +
DIM -

Quick

Connect

Driver

FIXTURE

DIM +
DIM -

PM3D

GROUND IN HOUSING

LINE

COM

Remote

Driver

DIM +
DIM -

Fixture
Fixture

GROUND ON PLATE

LINE

COM

Driver

DIM +
DIM -

PCIII

Quick

Connect

FIXTURE

LINE

Red

FIXTURE

COM

Remote

Driver

Black

DIM +
DIM -

MA/AP

GROUND

GROUND IN HOUSING

LINE

COM

Remote

Driver

DIM +
DIM -

DIM +
DIM -

Fixture

Fixture

Remote

Driver

Fixture

Fixture

LINE

COM

Remote

Driver

GROUND

F
Fixture -

GROUND IN HOUSING

LINE

COM

Remote

Driver

F
Fixture -

Remote

Driver

F
Fixture -

GROUND IN HOUSING

LINE

COM

Remote

Driver

F
Fixture -

WIRING DIAGRAM - INC Control Type

8.  Use waterproof wire connectors (By Others) to 

connect driver primary leads to branch circuit 

wires. Connect incoming ground to ground 

wire provided in UPM housing. Connect 

secondary leads to fixture leads. 

See wiring 

diagram.

Содержание SARATOGA Series

Страница 1: ...RM DRM Product must be installed by a qualified person in a manner consistent with its intended use and in compliance with the National Electrical Code Canadian Electrical Code and all Local and Provi...

Страница 2: ...rtight connections from remote driver to fixture leads using waterproof wire connectors By Others in splice location as per NEC Fixture Installation SARATOGA SERIES Remote Solid State LED Standard Ins...

Страница 3: ...pull out end cap assembly LED is still attached to leads Detach heatsink from fixture body via quick disconnect Twist and gently pull away optic from optic holder Do not pull on connector or wiring H...

Страница 4: ...refully pull out end cap assembly LED is still attached to leads Detach heatsink from fixture body via quick disconnect Loosen then remove two 2 8 32 screws from optic holder using 5 64 Allen wrench D...

Страница 5: ...ome extremely hot Do not touch hot lens or fixture body Do not touch the lamp at any time Use a clean dry soft cloth to handle the lamp Oil from skin may damage the lamp and cause it to rupture Replac...

Страница 6: ...ian Electrical Code and all Local and Provincial Codes Follow product label information and instructions Qualified Personnel with appropriate personal protective equipment must perform all servicing o...

Страница 7: ...wiring necessary for installation By Others Single Remote Driver 7 Connect branch circuit to terminal block Connect incoming ground to ground wire provided on NEMA 3R housing Connect secondary leads t...

Страница 8: ...alant Teflon tape adhesive etc Sealing the conduit after knockouts are removed is required to maintain warranty 8 Re attach cover Tighten cover screw 5 Pull branch circuit wiring necessary for install...

Страница 9: ...ck Connect incoming ground to ground wire provided on NEMA 3R housing Connect secondary lamp leads to terminal block See labels on terminal block for additional information 4 Connect conduit connector...

Страница 10: ...nd wire provided on NEMA 3R housing Connect secondary lamp leads to terminal A See labels on terminal block for additional information 4 Connect conduit connector through female threaded conduit entry...

Страница 11: ...an Electrical Code and all Local and Provincial Codes Follow product label information and instructions Qualified Personnel with appropriate personal protective equipment must perform all servicing of...

Страница 12: ...crews on Stability Flange to secure housing to EMT Remove excess EMT as needed 7 Per DIG IT Guide backfill the gap between the bottom of housing and bottom of hole with sand for drainage Housing Insta...

Страница 13: ...e watertight connections using waterproof wire connectors provided to leads on the bottom of Patented HydroLock Barrier Plate Assembly See wiring diagram s 5 Turn HydroLock Barrier Plate clockwise to...

Страница 14: ...EVERSE READ FOLLOW AND SAVE ALL SAFETY AND INSTALLATION INSTRUCTIONS 10 Remove any dirt or debris in O ring groove near top of housing Place O Ring inside of groove Failure to clean groove of debris w...

Страница 15: ...n Electrical Code and all Local and Provincial Codes Follow product label information and instructions Qualified Personnel with appropriate personal protective equipment must perform all servicing of...

Страница 16: ...back of the UPM housing Feed safety cable through opposing ends of the connector Pull on wires to assure the connection is secure Leave enough slack in safety cable for tree growth Adjustments can be...

Страница 17: ...ce with the National Electrical Code Canadian Electrical Code and all Local and Provincial Codes Follow product label information and instructions Qualified Personnel with appropriate personal protect...

Страница 18: ...n 2 Pullbranchcircuitwiringnecessaryforinstallation By Others 3 Install universal mounting ring IMPORTANT Orientation of universal ring will affect orientation of UPM Take note of mounting plate holes...

Страница 19: ...anadian Electrical Code and all Local and Provincial Codes Follow product label information and instructions Qualified Personnel with appropriate personal protective equipment must perform all servici...

Страница 20: ...with 5 64 Allen wrench on outside of UPM housing to lock in place Figure C IMPORTANT SAFETY INFORMATION LISTED ON REVERSE READ FOLLOW AND SAVE ALL SAFETY AND INSTALLATION INSTRUCTIONS Installation In...

Страница 21: ...rical Code Canadian Electrical Code and all Local and Provincial Codes Follow product label information and instructions Qualified Personnel with appropriate personal protective equipment must perform...

Страница 22: ...ack into place to renew seal integrity Installation Instructions PM2RM SURFACE MOUNT 10W Driver Housing 10 Make sure UPM housing gasket is free of any dirt or debris Attach the faceplate by tightening...

Страница 23: ...Electrical Code and all Local and Provincial Codes Follow product label information and instructions Qualified Personnel with appropriate personal protective equipment must perform all servicing of t...

Страница 24: ...READ FOLLOW AND SAVE ALL SAFETY AND INSTALLATION INSTRUCTIONS Ground Hot Neutral Installation Instructions PM2DRM TREE STRAP 10W Dual Driver Housing Red FIXTURE Hydrolock Plate Black D Driver White B...

Страница 25: ...ical Code Canadian Electrical Code and all Local and Provincial Codes Follow product label information and instructions Qualified Personnel with appropriate personal protective equipment must perform...

Страница 26: ...orientation of UPM Take note of mounting plate holes indicated with arrows on the universal ring holes to mount UPM in correct orientation Installation Instructions PM2DRM ROUND CAMLOCK 10W Dual Drive...

Страница 27: ...al Code Canadian Electrical Code and all Local and Provincial Codes Follow product label information and instructions Qualified Personnel with appropriate personal protective equipment must perform al...

Страница 28: ...hed orientation as shown Figure A 5 Rotate housing 90 counter clockwise Figure B Tighten set screw with 5 64 Allen wrench on outside of UPM housing to lock in place Figure C Installation Instructions...

Страница 29: ...ode Canadian Electrical Code and all Local and Provincial Codes Follow product label information and instructions Qualified Personnel with appropriate personal protective equipment must perform all se...

Страница 30: ...PM is designed as an installation aid and NOT a safety cable Do not add weight to or drop faceplate Red FIXTURE Hydrolock Plate Black Driver White Black Green Black White Hydrolock Plate Green Driver...

Отзывы: