Sensor and power supply in one case for onwall-, ceiling-
and flushmounting
Power supply:
230 V~ +6 %/-10 %
Power consumption:
< 1 W
Ambient temperature:
-25°C – +40°C
Degree of protection/class:
SM IP54, FC and FM IP20 / II
Settings:
locally and by remote control
Light values:
10 - 2000 Lux
Parallel operation:
Master/Slave
Area of coverage:
circular 360°
Range of coverage Ø H 2.5 m / T=18°C:
seated 6.4 m / tangential 24 m / radial 8 m
Recommended height for mounting:
2 - 3 m
Light measurement:
Mixed light, da artificial light
Lux values:
5 - 2000 Lux
• Relay/Channel 1 for light-connection
Type of contact
: NOC/with pretravel tungsten contact
Contact load:
2300 W, 230 V~, 10 A cos (
ϕ)
=1 /
1150 VA cos (
ϕ)
= 0.5
Max. no. of series-connected electronic ballasts:
depending on type and make, total connectable 140 µF.
DIM-Outputs:
PD4-DIM
1 x (1-10 V)
PD4-DUO-DIM 2 x (1-10 V)
Max. no. of series-connected electronic ballasts:
max. 50 electronic ballasts by one single supply with
max. 100 m cable run and a conductur cross-section of
0.75 mm²
Time-settings:
1 - 30 min. / test
Dimensions HxØ [mm]
SM
FC
FM
PD4-M-DIM
76 x 101 103 x 97 74 x 97
PD4-M-DUO-DIM
95 x 106 103 x 106 74 x 106
Visible portion when built into ceiling:
30 x 97 mm
Technical data PD4-Slave
Electrical data same as above, but just one channel for
signaling motion detection.
Declaration of Conformity:
The product complies with
the low voltage recommendation 2006/95/EC and the
EMV recommendation 2004/108/EC.
13. Technical data PD4-M-DIM/-DUO-DIM
10. Wiring diagrams
11. PD4-DIM/-DUO-DIM - Connections
Type
SM
FC
FM
PD4-DIM (Master)
92147
92247
92248
PD4-DUO-DIM (Master)
92271
92272
92273
PD4-S (Slave)
92142
92254
92163
LUXOMAT
®
Remote control:
IR-PDim (incl. wall bracket)
92200
Accessory:
BSK Ball basket guard
92199
Wall bracket for remote control as replacement 92100
Occupancy detectors - Covering IP23
92206
12. Article / Part-Nr. / Accessory
MAN 5
55
4
– 0
2_12/200
8
In case the sensing area of the LUXOMAT
®
PD4-DIM/
DUO-DIM is too large or areas are being covered that
should not be monitored, the range can be reduced or
limited through use of the enclosed masking clips (e).
9. Exclude sources of interference
8. Range of Coverage
6. Manual Dimming - Preset / User
(for IR-PDim functions see page 1)
You can dim manually by pressing the pushbutton
for a long time (> 2 sec). When the button is released,
the current dimming value is retained. Upon renewed
dimming, the dimming direction is reversed.
PRESET
–
the luminance set point is set during start-up
operation by the installer and remains unchanged.
The luminance set- point configured through manual
dimming is only applied for the time being.
Caution:
The constant light regulation is now deactivated!
The currently set artificial light is retained independent
of the ambient/daylight brightness!
After switching off and then back on, the originally set
luminance set-point is reset = constant light regulation
is activated.
USER
- can only be activated via the remote control!
The luminance set-point is changed upon each manual
dimming and re-adjusted by the user (Conformation
through relay clicking!)
The constant light regulation remains activated!
5.Fully / Semiautomaticmode
(for IR-PDim functions see page 1)
Fully automatic operation
In this operating mode, the lighting switches automati-
cally on and off for increased comfort, depending on
presence and brightness.
Semiautomatic operation
(Semiautomatic can only be activated via the remote
control!)
In this operating condition, in order to gain increased
savings, the lighting is energized only after being manu-
ally switched on. Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully
automatic one. However, the difference is that switching-
on must always be carried out manually!
As many (closer-contact) buttons as desired can be wired
in parallel on the “S” button input (ON/OFF Dimm).
7. Manual Switching
You can switch the lighting on and off manually
by pressing the pushbutton for a short time. It will
stay on or off as long as people are detected plus the
configured follow up time.
14. LED-functional indicators, fault-finding
The functional indicators in the case of the LUXOMAT
®
PD4-DIM/DUO-DIM-MASTER (red and green LED‘s)
Red LED indicating self-checking mode (over a period
of 60 seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second
EEPROM/memory empty
Flashing rapidly
EEPROM/memory contains information
Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for
commands from the remote control
Illuminated for 2 seconds
Signal validly received
Illuminated for 0.5 seconds
Not-accepted command, detector blocked
Flashing extremely rapidly
Not-accepted command, occurs, for example, when
an attempt is made to input twilight-value are too
bright or too dark
Green LED as an acknowledgement of receipt for
commands from the remote control
Lights up for 3 seconds
Semi automatic or user signal correctly received
Green LED as an indicator of status (only for status
“Permanent protection against sabotage”
)
Flashing irregularly
Movement are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
lluminated for 2 seconds
Signal validly received
(dependent upon operating mode)
PD4-DIM
PD4-DUO-DIM
Push button operation
For manual switching push
the button only a short time (0.2 - 0.5 sec.)! To dim
push the button until the wished light level is arrived.
Separate reading of the lux levels for both
channels, but only one switching channel!
For manual switching push the button only a short
time (0.2 - 0.5 sec.)! To dim push the button until the
desired light level is arrived.
1-10 VDC
Terminal connection for master-/ slave-operation
MASTER
SLAVE
R R N N L L
R
L' N L S + -
Terminal connection PD4-M-DUO-DIM
Channel 1
1-10 VDC
Channel 2
1-10 VDC
SLAVE
R S L L' N
+ +
Master-/ slave-operation. The master is the only one
to read the light level and to switch the connected
loads. Independant of the light level the slave units
react to movements only by sending impulsions via
the dry contact.
No load can be connected to the dry
contact. The master-dim-occupancy detec-
tors can not be switched into parallel. For
that application please prefer the master- /
slave-installation. It is recommended to put
the master the furthest possible postion
away from the natural light source.
1-10
VDC
Terminal connection for push button operation
MASTER
+
R L' N L S
24 m
8 m
6.4 m
24 m
360°
Mounting height
2.5 m
1
2
walking across
walking towards
seated
e
Connection PD4-DUO-DIM-FM/-FC/-SM
Connection example PD4-DIM-FM
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
+
+
–
N
L' L
S
R
+2
+1
–
1-10 V
SLAVE
1-10 V
+
–
N
L' L
S
R
+
–
SLAVE
1-10 V
max
50
Lux
1500
Lux
ON
OFF
2
1
12 m
12 m
8 m
6.4 m
24 m
360°
Mounting height
2.5 m
2
1
quer zum Melder gehen
frontal zum Melder gehen
sitzende Tätigkeit