8 – Error codes and what to do: 

This table explains the error codes caused by a defective 

regulating component or by a security operation. 

 

Screen and state 
of the heat water 

pump 

Component 

Possible 

Intervention 

Second reason if 

the intervention 

is without effect 

PP 01 
Compressor and fan 
stopped 

Water temperature 
sensor 

Sensor disconnected, 
non supplied or 
defective 

Check the connections, the wires, 
change it or replace the electronic card 

PP 02 
Compressor and fan 
stopped 

compressor 
exhaust 
temperature 
sensor 

Sensor disconnected, 
non supplied or 
defective 

Check the connections, the wires, 
change it or replace the electronic card 

EE 01 

Compressor and fan 
stopped 

High pressure,   
Low pressure 
protection 

Insufficient water 
flow 

Check the water flow 

Pressure switch out 
of order 

Replace the pressure switch Have 

Too much refrigerant 
gas present 

the heat pump checked by a 
refrigeration technician 

EE 02 

Compressor and fan 
stopped 

Low pressure 
protection 

Not enough 
refrigerant gas 

Have the heat pump checked by a 
refrigeration technician 

Leak in the cooling 
conduits 

Have the heat pump checked by a 
refrigeration technician 

EE 03 

Compressor and fan 
stopped

 

Flow switch 

Flow switch 
disconnected, non 
supplied or defective 

Check the connections, the wires, 
change it or replace the electronic card 

EE 04 
The unit cannot be 
started 

Emergency switch 

Emergency switch 
disconnected 

Check the connections and the wires 

EE 06 
Compressor and fan 
stopped 

compressor 
exhaust 
temperature 
sensor 

Compressor exhaust 

temperature 
detected up to 95°C 
more than 3 times in 
1HR 

Environment problem 
Refrigerant leakage 
Capillary is half blocked 

EE 08 

The wire control 
can't operated

 

Wire control 
Communication 
error 

Signal cable of wire 
Control is loose 

Check the connection of signal cable 

 

18 

Содержание BP-50WS-C

Страница 1: ...Directions for installation and maintenance...

Страница 2: ...explored view Wire control operation General diagram of the refrigerating circuit Safety and control systems Electric diagram 5 Installation p12 Rules of installation Hydraulic connections Electric c...

Страница 3: ...se not in conformity and random will be considered as dangerous and unsuitable The assembly the electric connection and the start up must be carried out by specialized and professional person When con...

Страница 4: ...e complete state of the machine 4 Technical description Characteristics MODEL BP 50WS C Power supply 230V 50Hz Heating consumption power kW 0 9 Heating restored power kW 4 6 Heating nominal intensity...

Страница 5: ...ntrol panel 5 Fast connection for water outlet 6 Refrigerant pressure manometer 7 Wire connection for power supply 8 Fast connection for water intlet 9 Evaporator 10 Fan 11 Compressor 12 High and low...

Страница 6: ...6...

Страница 7: ...unning press or to enter operation parameter check interface But can t change parameters Except the parameter 0 for water temperature setting If the heat pump is running the LED display shows current...

Страница 8: ...ime displayed and ON to blink press TIMER ON botton again Change the hour using the and keys Press TIMER ON botton again to change the minutes using the and keys Press TIMER ON botton again the end Pr...

Страница 9: ...ressure and in temperature by the compressor which sends it in the condenser exchanger where it loses its heat in giving it to the water of swimming pool and comes back in liquid state it loses its pr...

Страница 10: ...ettings than this required With 4 safety systems A water flow detector placed at the exit of the exchanger A high pressure gas circuit breaker a low pressure gas circuit breaker An outlet compressor t...

Страница 11: ...11 Electric diagram...

Страница 12: ...place the fan would recycle its air and the Heat pump would be down performance The fan should not blow towards the windows or crossing point Safety distance between the swimming pool and the foot ba...

Страница 13: ...nd connect the pipe if need Hydraulic connections To respect imperatively Connection is carried out with a by pass located on the circuit of filtration upstream appliances of the chemical treatment of...

Страница 14: ...rotect the Heat pump exclusively the circuit breaker must be specified with curve D the fuse must be specified Am Differential protection 30 mA the length of cable between the connector block of the h...

Страница 15: ...tion the swimming pool water into the pipes Engage the circuit breaker of pump of filtration Set the water temperature into the swimming pool adjustable from 15 C to 40 C The heat pump heats until the...

Страница 16: ...at Pump in these conditions the totality of the water flow goes by the Heat Pump Put into service the Heat Pump in heating mode wait for the indicated pressure being stabilized the correct setting of...

Страница 17: ...mes more electricity The temperature sensors compressor outlet and the magnetic circuit breaker on the compressor power supply protect the compressor from these extreme conditions the error messages E...

Страница 18: ...he pressure switch Have Too much refrigerant gas present the heat pump checked by a refrigeration technician EE 02 Compressor and fan stopped Low pressure protection Not enough refrigerant gas Have th...

Отзывы: