6- Water Flow and refrigerating circuit pressure 

 

 
After putting into service, do the settings of pressure of the refrigerant circuit 

for having an optimal operating of the heat pump, following:   

 
 
Stage 1: 
Before starting the Heat Pump, ambient   
temperature around 20°C, refrigerant meter 
shows pressure from 14 to 16kg/cm². 
 
 
 
Stage 2: 
Close completely the by pass valve and open   
large inlet and outlet valves of the Heat   
Pump; in these conditions the totality of the   
water flow goes by the Heat Pump. 
Put into service the Heat Pump in heating mode, wait for the indicated 

pressure being stabilized; the correct setting of the pressure is from 21 to 35 
kg/cm²; 

In most of cases (pump of filtration given a flow until 20m

³

/h) you do not have 

to open the by pass valve. 

If the stabilized pressure is under 21kg/cm², the progressive opening of the by 

pass valve will allow rising this pressure. 

 
The adjustment of the by pass valve done, you have in principle no reason to 

modify it during the season. See the paragraph “Environment problem” too. 

 
 

 

 
 
 
 
 
 
 
 
 

 
 

Содержание BP-50WS-C

Страница 1: ...Directions for installation and maintenance...

Страница 2: ...explored view Wire control operation General diagram of the refrigerating circuit Safety and control systems Electric diagram 5 Installation p12 Rules of installation Hydraulic connections Electric c...

Страница 3: ...se not in conformity and random will be considered as dangerous and unsuitable The assembly the electric connection and the start up must be carried out by specialized and professional person When con...

Страница 4: ...e complete state of the machine 4 Technical description Characteristics MODEL BP 50WS C Power supply 230V 50Hz Heating consumption power kW 0 9 Heating restored power kW 4 6 Heating nominal intensity...

Страница 5: ...ntrol panel 5 Fast connection for water outlet 6 Refrigerant pressure manometer 7 Wire connection for power supply 8 Fast connection for water intlet 9 Evaporator 10 Fan 11 Compressor 12 High and low...

Страница 6: ...6...

Страница 7: ...unning press or to enter operation parameter check interface But can t change parameters Except the parameter 0 for water temperature setting If the heat pump is running the LED display shows current...

Страница 8: ...ime displayed and ON to blink press TIMER ON botton again Change the hour using the and keys Press TIMER ON botton again to change the minutes using the and keys Press TIMER ON botton again the end Pr...

Страница 9: ...ressure and in temperature by the compressor which sends it in the condenser exchanger where it loses its heat in giving it to the water of swimming pool and comes back in liquid state it loses its pr...

Страница 10: ...ettings than this required With 4 safety systems A water flow detector placed at the exit of the exchanger A high pressure gas circuit breaker a low pressure gas circuit breaker An outlet compressor t...

Страница 11: ...11 Electric diagram...

Страница 12: ...place the fan would recycle its air and the Heat pump would be down performance The fan should not blow towards the windows or crossing point Safety distance between the swimming pool and the foot ba...

Страница 13: ...nd connect the pipe if need Hydraulic connections To respect imperatively Connection is carried out with a by pass located on the circuit of filtration upstream appliances of the chemical treatment of...

Страница 14: ...rotect the Heat pump exclusively the circuit breaker must be specified with curve D the fuse must be specified Am Differential protection 30 mA the length of cable between the connector block of the h...

Страница 15: ...tion the swimming pool water into the pipes Engage the circuit breaker of pump of filtration Set the water temperature into the swimming pool adjustable from 15 C to 40 C The heat pump heats until the...

Страница 16: ...at Pump in these conditions the totality of the water flow goes by the Heat Pump Put into service the Heat Pump in heating mode wait for the indicated pressure being stabilized the correct setting of...

Страница 17: ...mes more electricity The temperature sensors compressor outlet and the magnetic circuit breaker on the compressor power supply protect the compressor from these extreme conditions the error messages E...

Страница 18: ...he pressure switch Have Too much refrigerant gas present the heat pump checked by a refrigeration technician EE 02 Compressor and fan stopped Low pressure protection Not enough refrigerant gas Have th...

Отзывы: