Azbil NX-S11 Скачать руководство пользователя страница 8

E2

OVERVIEW

Linked by Ethernet, Network Instrumentation Modules make dis-

tributed instrumentation, high-speed communications, and easy in-

stallation all possible at the same time. The module also creates value 

for customers by offering reduced environmental impact, superior 

product quality, and higher productivity.
The Supervisor Module is a modular controller designed to execute 

either multi-loop cooperative control in combination with multiple 

other control modules.  The NX-S11/12/21 is equipped with one of 

three different types of multi-loop cooperative control function.

MODEL SELECTION TABLE

 

„

Supervisor module

Basic 

Model 

No.

Type

Ring 

connection

Option

Addition

1 2 3

NX-

Network Instrumentation 

Module

S11

Supervisor module Control 

of Temperature difference 

between zones

S12

Supervisor module op-

tional start-up control

S21

Supervisor module peak 

power suppression control

N

Non-ring communications

R

Ring communications

0

None

00

None

0

None

1

With fault DO

0

None

D

Inspection certificate

T

Tropicalization treatment

K

Anti-sulfide treatment

B

Tropicalization tre 

Inspection certificate

L

Anti-sulfide tre 

Inspection certificate

NAMES OF PARTS

 

„

Main unit

Indicators on the module vary depending on the model No. 

(functions).

LED operation indicators

PWR

RUN

MOD

COM

NST

FAIL

Loader jack

Push button

Forced IDLE switch

485: RS-485 indicator

DO: Fault DO indicator

(Option)

BAT: Battery indicator

Fault DO connector

(Option)

 

„

Base

Power supply terminal:

1: 24 V DC (+)

2: 24 V DC (−)

DIN rail locking tab:

Used for locking on a DIN rail.

RS-485 communications terminal:

3 wire RS-485 connector terminal

4: DA (+)

5: DB (−)

6: SG

Side connector:

Used for connecting 

modules.

RS-485 cutoff switch:

Used to disable 

RS-485 communications 

with devices connected 

on the right side.

CONNEC

T

Enlarged view

Communications 

enabled

(default setting)

CONNEC

T

Communications

disabled

CONNEC

T

INSTALLATION

 

„

Installation location

Install modules indoors. Minimum clearances are shown in 

figures.

Wiring duct, etc.

NX

NX

50 mm

50 mm

W

ir

ing duc

t, et

c.

50 mm

W

ir

ing duc

t, et

c.

80 mm

From the front

Wiring duct, etc.

50 mm*

50 mm*

50 mm

Wiring duct, etc.

Wiring duct, etc.

Note:  If used with devices other than this module, check the specifications 

of the devices, and choose the larger of the recommended space in 
each direction.

Install the controller in a location that meets the following criteria:

• 

No high/low temperature/humidity.

• 

Free from sulfide gas or corrosive gas.

• 

Not dusty or sooty.

• 

Protected from direct sunlight, wind, and rain.

• 

Little mechanical vibration or shock.

• 

Not close to high voltage line, welding machine or other elec-

trical noise generating source.

• 

At least 15 meters away from the high voltage ignition device 

for a boiler.

• 

No strong magnetic fields.

• 

No flammable liquid or gas.

• 

Indoors

• 

I/O common mode voltages: voltage to ground is 30 Vrms 

min., 42.4 V peak min., and 60 V DC min.

 

„

Linking modules

The NX-S11/12/21 can be linked to other modules using the con-

nectors on the left and right of the base.
When linked, modules share the power supply and RS-485 con-

nection, eliminating the need for wiring. The connection with the 

module on the right can be disabled using the RS-485 communi-

cations cutoff switch on the base.

*  The clearance required for battery replacement 

when the power is on is 60 mm or more.

Содержание NX-S11

Страница 1: ...J1 CP UM 5557JE NX NX S11 12 21 URL https www azbil com jp product factory order html DIN 2 60 81447729 001 NX S11 12 21 NX S11 12 21 1 CP UM 5557JE...

Страница 2: ...COM NST FAIL IDLE AUTO BAT 485 DO LED PWR RUN MOD COM NST FAIL IDLE 485 RS 485 DO BAT 1 DC24 V 2 DC24 V DIN DIN RS 485 3 RS 485 4 DA 5 DB 6 SG RS 485 RS 485 CONNECT CONNECT CONNECT NX 50 mm 50 mm 50 m...

Страница 3: ...J3 2 mm RS 485 M3 60 cm 60 NX S21 60 DO DO DO 2 DO 1 2 DO COM or 1 2 DO 1 2 DO COM...

Страница 4: ...2 LIM Limited energy circuit 1 25 mm2 16AWG 30 m M3 5 8 mm 0 6 N m 1 70 W RS 485 CPL Modbus RS 485 1 2 4 5 6 DA DB SG 150 5 1 2 W SG RS 485 LED RS 485 UL UL OFF OFF OFF 60 10 ON 3 OFF SLP NX OFF 60 O...

Страница 5: ...s2 10 150 Hz XYZ 2h 0 300 m s2 DIN 3 60 cm 1 3 6 ROM SRAM ROM 10 DC500 V 20 M I O AC500 V 1 min I O 4W 10 s 12 A 30 100 85 mm PPO EN61326 1 For use in industrial locations UL61010 1 DIN 0 6 0 1 N m 2...

Страница 6: ...3u 10BASE T 100BASE TX Auto MDI MDI X 3 4 0 3 1 IEEE802 3u 100BASE TX Full Duplex Auto MDI MDI X 4 1 IEEE802 3u 100BASE FX Full Duplex 1300 nm 100BASE TX RJ 45 100BASE FX 2 LC 100BASE TX UTP 4P Cat5e...

Страница 7: ...ght cause fire or device failure Do not touch live parts such as the power terminals Doing so might cause electric shock Before wiring the NX S11 12 21 be sure to turn the power OFF Failure to do so m...

Страница 8: ...ail RS 485 communications terminal 3 wire RS 485 connector terminal 4 DA 5 DB 6 SG Side connector Used for connecting modules RS 485 cutoff switch Used to disable RS 485 communications with devices co...

Страница 9: ...en wiring this device observe local electrotechnical standards Do not run wires outside The equipment could be damaged in the event of lightning When connecting wires to the power terminals use crimp...

Страница 10: ...certified product Battery replacement The backup battery can be replaced whether the power is turned on or off Handling Precautions To replace the battery with the power off make sure that the power...

Страница 11: ...ting conditions Power ON operation delay Requires approx 10 s before normal operation begins under standard conditions Inrush current 12 A max under operating conditions External dimensions 30 100 85...

Страница 12: ...n adaptor used as a chain connection ring communications terminal Ethernet path in the base zReplacement battery sold separately model No 81447729 001 Configuration Button battery with connection cabl...

Отзывы: