1-3 Peak hold and bottom hold
The peak or bottom flow rate can be displayed.
Handling Precautions
• The displayed channel can be changed during hold.
• If the power is turned OFF, the peak hold or
bottom hold is cancelled.
• Peak hold and bottom hold cannot be done at
the same time.
• When the indication hold function is activated,
the output hold function is also activated at the
same time.
1-4 Flow rate display moving average setting
The flow rate moving average shown on the 7-seg-
ment LED can be set.
Flow rate display moving average setting
f- 1
: Disabled (display updated every 125 ms)
f-2
: Twice
f-3
: 4 times
f-4
: 8 times
2 Basic settings
2-1 Flow sensor selection
The desired flow sensor can be set for each channel.
Flow sensor settings
SE 1
: MCS100A100 (-3 to +3L/min)
SE2
: MCS100A104 (0 to 3L/min)
SE3
: MCS100A108 (-500 to +500mL/min)
SE4
: MCS100A112 (0 to 500mL/min)
SE5
: MCS100A120 (0 to 10L/min)
2-2 Operation mode selection
The desired operation mode can be set for each channel.
Operation mode settings
C0 1
: Window comparator mode 1
C02
: Window comparator mode 2
C03
: Window comparator mode 3
C04
: Window comparator mode 4
2-3 Threshold settings (L1 (
∆
L)/L2)
The desired threshold flow rate can be set for each channel.
Threshold flow rate settings
1 1
: 1ch_L1/
∆
L
3 1
: 3ch_L1/
∆
L
12
: 1ch_L2
32
: 3ch_L2
2 1
: 2ch_L1/
∆
L
4 1
: 4ch_L1/
∆
L
22
: 2ch_L2
42
: 4ch_L2
Handling Precautions
• If the threshold flow rate is set such that L1
≤
L2, the switch output does not turn ON.
• “L1
≤
L2” may also come about when
∆
L is
set in window comparator mode 2 or 3, due to
reading of the reference value, with the result
that the switch output does not turn ON.
2-4 Hysteresis settings
The desired hysteresis can be set for each channel.
Hysteresis settings
H S 1
: Ch. 1
H S3
: Ch. 3
H S2
: Ch. 2
H S4
: Ch. 4
Handling Precautions
• To prevent chattering, set the hysteresis value
to 2 or more.
3 Advanced settings
3-1 Reading the reference flow rate (window
comparator mode 2 or 3)
When window comparator mode 2 or 3 is used, the
reference flow rate may be read.
Enabled channel settings
aEF 1
: Ch. 1
aEF3
: Ch. 3
aEF2
: Ch. 2
aEF4
: Ch. 4
3-2 Zero point adjustment (zero reset)
The zero point can be adjusted for each channel.
Zero point adjustment settings
b- 1
: Ch. 1
b-3
: Ch. 3
b-2
: Ch. 2
b-4
: Ch. 4
Handling Precautions
• If the power is turned OFF, the zero point
adjustment is cancelled.
selects channel
Zero point is adjusted
(At same time)
or
b-
1
SEf
1
SEf2
SEf3
SEf
1
2
3
4
5
6
Steps
Key operation
7-seg. LED
Remarks
selects channel
(At same time)
The reference flow value is
available
or
AEF
1
SEf
1
SEf
1
2
3
4
Steps
Key operation
7-seg. LED
Remarks
F
F
F
F
selects channel
(At same time)
sets hysteresis
Hysteresis is set
or
or
0.02
SEf
1
SEf2
HfS
1
SEf
1
2
3
4
5
Steps
Key operation
7-seg. LED
Remarks
Steps
Key operation
7-seg. LED
Remarks
selects channel
sets threshold rate
Threshold flow rate is set
or
or
1
1
SEf
1
SEf
1
2
3
4
5
selects channel
selects output mode
(At same time)
Output mode is set
or
or
CH
1
C0
1
SEf
1
SEf
1
2
3
4
5
Steps
Key operation
7-seg. LED
Remarks
selects channel
selects flow sensor
(At same time)
Flow sensor is set
Steps
Key operation
7-seg. LED
Remarks
or
or
CH
1
SE
1
SEf
1
SEf
1
2
3
4
5
or
Select the flow rate display moving
average setting by pressing
Flow rate display moving average
setting is activated
f-
1
SEf
1
SEf2
SEf3
SEf
1
2
3
4
5
6
Steps
Key operation
7-seg. LED
Remarks
1
2
3
4
5
6
7
bHL
SEf
1
SEf2
SEf3
SEf4
SEf
SEf
1
SEf2
SEf3
SEf4
SEf
PHL
Hold start
(At same time)
(At same time)
(At same time)
(At same time)
Peak hold
Bottom hold
7-seg. LED
Remark
Cancelled
Steps
7-seg. LED
4