HyperTerminal setup

(1) From the 

[File]

menu, select

[Properties]

to open the screen

shown in the figure below. Set

[Connection Method]

. Click the

[Modem Setting] 

button.

(2) Set the communications settings

as shown:

Transmission speed (B): 9600
Date length (D):

8

Parity (P):

Odd

Stop bit (S):

1

Flow control (F):

Xon/Xoff

Then, click the

[OK] 

button.

(3) Click the 

[Settings]

tab seen in

step (1), and the screen shown in
the figure below will appear.
Click the 

[ASCII Settings] 

button.

(4) Configure the settings as shown

below and click 

[OK]

. The screen

returns to that shown in step (3).
Click 

[OK]

again.

Specifications

External dimensions

Panel cutout dimensions

A. S. OUT

SW.OUT

ch

1

2

3

4

40

27.6

35.4

32

40

Note: Dimensions exclude mounting 
          part and mounting retainer

70

70

45

+0.6  0

45

+0.6

 0

Unit: mm

Unit: mm

Item

Specification

Flow rate display

7 segment LED, 3 digit display

Flow rate display 

Selectable from: disabled, 2, 4, and

moving average function

8 times

(shown every 125 ms)

• 

Disabled: no moving average display

• 

Twice: average of 2 flow rates every 

125 ms

• 

4 times: average of 4 flow rates every 

125 ms

• 

8 times: average of 8 flow rates every 

125 ms

Output indication (SW.OUT) Red LED lights up when output is ON

Auto scan channel 

Green LED for the displayed 

display

channel lights up

Console keys

: up, 

: down, 

: mode

Communications

RS-232C communications

Operating temperature  -10 to +50°C (without condensation

without freezing)

Storage temperature 

-20 to +80°C (without condensation
without freezing)

Dielectric strength

500Vac 1min

Insulation resistance

100M

or more (500Vdc megger)

Vibration resistance

88.3 m/s

2

(total amplitude 1.5mm 10 to

55Hz)

Shock resistance

490 m/s

2

(non-repeated shock)

Case material

PBT

Mass

Approx. 45g (without cables)

Item

Specification

Power

24Vdc +/- 10%

Supply voltage for flow  24Vdc +/- 10%
sensor

Current consumption 

100mA max (not including flow sensor
current)

Applicable sensor type MCS100A100 (-3 to 3 L/min)

MCS100A104 (0 to 3L/min))
MCS100A108 (-500 to 500mL/min)
MCS100A112 (0 to 500mL/min)
MCS100A120 (0 to 10L/min)

Number of connected 

1 to 4 

sensors

Input voltage range

1 to 5Vdc

Maximum applied voltage 5.3Vdc

Number of outputs

4

Output type

NPN open collector

Response time 

3 ms (Response time before the switch
output turns on is variable and can be
selected from 3, 20, 100, and 1000 ms.)

Load voltage

30Vdc or less

Load current

50mA or less
If a load current exceeding 70 mA
continues for 5 ms or longer, error 

E-2n

is displayed by the overcurrent
protection function.

Internal voltage drop

0.3V max. (with 5mA load current)

Operation mode

Window comparator modes 1 to 4

Output mode

Effective only in window comparator 

(inverted / direct)

mode 4

Hysteresis

Variable (set to "2" or more)

Voltage

Sensor input

Switch output

Display

Setting method

General

Specifications are subject to change without notice.

(09)

1-12-2 Kawana, Fujisawa
Kanagawa 251-8522 Japan

URL:

http://www.azbil.com

1st edition: Oct. 2006 (U)

3rd edition: Apr. 2012 (M)

Содержание MCW400A100

Страница 1: ...thout notice Considerable effort has been made to ensure that this manual is free from inaccuracies and omissions If you should find an error or omission please contact the azbil Group In no event is...

Страница 2: ...ion part stands above the connector main body as shown in the figure below If the connector cover is not lifted off the connector main body it cannot be used 1 Cut the cable to the required length Rem...

Страница 3: ...scanning indication Auto scanning indication at all channels is available Handling Precautions Since the auto scanning mode is also used for the key lock function key operations other than auto scann...

Страница 4: ...h channel Hysteresis settings H S 1 Ch 1 H S3 Ch 3 H S2 Ch 2 H S4 Ch 4 Handling Precautions To prevent chattering set the hysteresis value to 2 or more 3 Advanced settings 3 1 Reading the reference fl...

Страница 5: ...erase write cycles to exceed the guaranteed amount Window comparator mode 4 L1 and L2 can be set to desired levels Hardware requirement PC PC 98 series or equivalent DOS V machine OS Windows 95 or lat...

Страница 6: ...0L min MODE1 1 1 Ch 1 2 Ch 2 3 Ch 3 4 Ch 4 1 Window comparator mode 1 2 Window comparator mode 2 3 Window comparator mode 3 4 Window comparator mode 4 P1 1 Ch 1 2 Ch 2 3 Ch 3 4 Ch 4 HYS1 1 1 Ch 1 2 Ch...

Страница 7: ...on ON or OFF Command example BHL 1 CR LF Response example OK CR LF DLY Function Sets the switch output response time for any channel Command example DLY1 2 CR LF Response example OK CR LF SD Function...

Страница 8: ...without condensation without freezing Storage temperature 20 to 80 C without condensation without freezing Dielectric strength 500Vac 1min Insulation resistance 100M or more 500Vdc megger Vibration re...

Отзывы: