AB-5963 

Wiring port

Seal connector 
(with separate order required)

Installing Models HTY7913, HY7913 series 
(for equipment, including chamber and thermometer 
shelter, insertion) 

1)  Prepare the dedicated mounting bracket.  Attach the 

indicator label for mounting hole at the probe mounting 
position, and make a mounting hole on the equipment 
panel. 

 

 

 

 

 

 

 

Figure 7.  Indicator label on the panel 

 

2)  Fix the mounting bracket onto the equipment panel with 

M4 screws (supplied with the bracket). (The side with 
shorter protruding part needs to face outward. See Fig. 
8.) 

 

 

 

 

 

 

Figure 8.  Mounting bracket on the panel 

 

3)  Turn the main unit stopper 45 degrees (from ‘a’ to ‘b’ 

shown in Fig. 9) to unlock, and insert the probe of the 
main unit into the bracket as the main unit claws and the 
bracket slits match. 

 

 

 

 

 

 

 

 

 

Figure 9.  Mounting the main unit on the panel  

(with the mounting bracket) 

4)  Completely insert the probe into the panel.  Then, fix the 

probe and the bracket by turning the stopper 45 degrees 
(from ‘b’ to ‘a’ shown in Fig. 10) to lock. 

 

 

 

 

 

 

 

 

Figure 10. Fixing the main unit on the panel 

(with the mounting bracket) 

 
Wiring (common to Models HTY7903/HY7903 and 
HTY7913/HY7913 series) 

Wiring procedure 

1)  Open the front cover by pressing the claw of the case. 

(See ‘a’ in Fig. 11.)  At this time, open 30 degree wide or 
wider. (See ‘b’ in Fig. 11.)  Then lift the front cover to 
detach. (See ‘c’ in Fig. 11.) 

 

 

 

 

 

 

 

Figure 11.  Detaching the front cover 

 

2)  Lead the cable through the wiring port. 

 

Seal connector connection 
Prepare the appropriate seal connector (with separate 
order required), depending on the quantity of core cables.  
Screw the threaded seal connector onto the wiring port 
and lead the cables through the port. 

 

 

 

 

 

 

 

 

 

 

 

Figure 12.  Seal connector connection 

Mounting 
bracket 

Panel  

Side view

Stopper 

 
Claw 

Main unit of 
Model HTY7913/ 
Model HY7913 

45

°

 

Indicator label 

Panel  

b a 

a. Press. 

Claw

b. Open.

c. Detach.

Содержание HTY7903T

Страница 1: ...t is suitable for various applications such as a duct or chamber for building air conditioning and outdoor air measurement as well as industrial applications Model HY79X3 series for dewpoint temperatu...

Страница 2: ...is necessary to minimize lightning damages to the product Always disconnect power source before performing any wiring to prevent equipment damages Use crimp terminal lugs with insulation for electric...

Страница 3: ...Model number Description Insertion length HTY7903T1P00 Dewpoint temperature 1 5 V temperature Pt100 Long HTY7903T4P00 Dewpoint temperature 4 20 mA temperature Pt100 Long HTY7903T6P00 Dewpoint tempera...

Страница 4: ...0 Power consumption Models HTY79X3T1 HY79X3T1 series with 1 5 V output Models HTY79X3T4 HY79X3T4 series with 4 20 mA output Models HTY79X3T6 HY79X3T6 series with 0 10 V output 0 7 VA for 24 V AC 600 m...

Страница 5: ...ls HTY7903 HY7903 series Models HTY7913 HY7913 series Mounting bracket Part No 83157235 001 Figure 1 Dimensions mm 70 247 6 A A 51 3 45 6 67 3 113 5 110 20 70 108 6 51 3 45 6 67 3 113 5 110 20 30 25 5...

Страница 6: ...t Figure 2 Indicator label on the duct 2 Fix the mounting bracket onto the duct with M4 screws supplied with the bracket inserting packing between the duct and the bracket The side with longer protrud...

Страница 7: ...nel with the mounting bracket 4 Completely insert the probe into the panel Then fix the probe and the bracket by turning the stopper 45 degrees from b to a shown in Fig 10 to lock Figure 10 Fixing the...

Страница 8: ...seal connector connection Figure 16 Tightening the seal connector Figure 17 Connection of 7 and 4 core cables to terminals CAUTION Make sure all the wires are tightly connected to prevent heat generat...

Страница 9: ...19 Correct wiring separate 24 V AC transformers 24 V DC Transformer shared with two sensors Fig 20 shows wiring example of Model HY78X3T For connecting terminals and E 3 and 2 use power with 0 022 F...

Страница 10: ...oint single point calibration Replace the sensor Filter replacement CAUTION Installation must be performed by qualified personnel in accordance with all applicable safety standards IMPORTANT Be sure n...

Страница 11: ...le measuring instrument for single point calibration with correct procedure in appropriate environment Calibrated digital multimeter is recommended to check output Figure 26 Single point calibration M...

Страница 12: ...AB 5963 Specifications are subject to change without notice Building Systems Company http www azbil com Rev 6 0 Sep 2015 AB 5963 J AI 5963 Rev 5 2 Printed in Japan 12...

Отзывы: